![Omron C200HE-CPU -Z Series Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/omron/c200he-cpu-z-series/c200he-cpu-z-series_installation-manual_742479128.webp)
113
Appendix B
Specifications
The following figures and tables provide specifications for each Unit of the C200HX/C200HG/C200HE. I/O Units
may take on one of two different shapes and are sometimes referred to as A-shape Units or B-shape Units.
Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape
Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of
these two shapes of I/O Unit.
General Specifications
Item
Specifications
Power Supply
Unit
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200H-PA209R
C200HW-PD024
Supply voltage
100 to 120 VAC/200 to 240 VAC (50/60 Hz)
24 VDC
Operating voltage
range
85 to 132 VAC/170 to 264 VAC
19.2 to 28.8 VDC
Power
consumption
120 VA max.
180 VA max.
40 W max.
Inrush current
30 A max.
30 A max. at 100
to 120 VAC
40 A at 200 to
240 VAC
30 A max.
Output capacity
5 VDC, 4.6 A (including power supply to the CPU Unit)
5 VDC, 9 A
(including power
supply to the CPU
Unit)
5 VDC, 4.6 A
(including power
supply to the CPU
Unit)
26 VDC, 0.625 A
Total: 30 W
26 VDC, 0.625 A
24 VDC, 0.8 A
Total: 30 W
26 VDC, 0.625 A
Total: 30 W
26 VDC, 1.3 A
Total: 45 W
26 VDC, 0.625 A
Total: 30 W
Output terminals
Without
With
(see note 1)
Without
Without
RUN output
(see note 5)
Without
SPST-NO contact
Switching
capacity:
2 A at 250 VAC
(resistive load),
0.5 A at 250 VAC
(inductive load),
2 A at 24 VDC
SPST-NO contact
Switching
capacity:
2 A at 240 VAC
(resistive load),
0.5 A at 120 VAC
(inductive load),
2 A at 24 VDC
(resistive load), 2
A at 24 VDC
(inductive load)
Without
Insulation
resistance
AC: 20 M
Ω
min. (at 500 VDC) between external terminals and GR terminal
(see note 2)
DC: 20 M
Ω
min.
(at 500 VDC)
between external
terminals and GR
terminal (see note
2)
Dielectric strength
AC: 2,300 VAC, 50/60 Hz for 1 minute between external terminals and GR
terminals with a leakage current of 10 mA max. (see note 2)
DC: 1,000 VAC,
50/60 Hz for 1
minute between
external terminals
DC: 1,000 VAC, 50/60 Hz for 1 minute between external terminals and GR
terminals with a leakage current of 10 mA max. (see note 2)
external terminals
and GR terminals
with a leakage
current of 10 mA
max. (see note 2)
Содержание C200HE-CPU -Z Series
Страница 1: ...Cat No W302 E1 09 Programmable Controllers C200HX CPUjj E ZE C200HG CPUjj E ZE C200HE CPUjj E ZE...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ......
Страница 23: ......
Страница 63: ......
Страница 109: ......
Страница 127: ......
Страница 212: ...Appendix B Specifications 197 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 227: ......
Страница 233: ......