Appendix B
Specifications
147
the ALARM output or by connecting an alarm output indicator. It’s not possible to connect both the Input Unit
and the indicator at the same time. Unless the external I/O power supply is connected and turned ON, the
indicator will not light even if the output contact turns ON.
Terminal Connections
+24 VDC
24 VDC
0 V
Note When the ALARM output turns ON, remove the cause of the high current and then shut off the external
power supply for approx. 1 second. After confirming that the cause has been removed, turn ON the power
supply again to reset the output. As shown in the diagram, it is recommended that a relay or switch that turns
ON or OFF only the external power supply be connected right before the B9 (+V). Check that this relay or
switch has a contact capacity higher than the external power supply current consumption (35 mA + load
current minimum).
Triac Output Unit C200H-OA122-E
Max. Switching Capacity
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
Max. Inrush Current
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
Min. Switching Capacity
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
Leakage Current
1.5 mA (120 VAC) max.
Residual Voltage
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
ON Response Time
1 ms max.
OFF Response Time
1/2 of load fr1 ms or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
E-shape
Содержание C200HE-CPU -Z Series
Страница 1: ...Cat No W302 E1 09 Programmable Controllers C200HX CPUjj E ZE C200HG CPUjj E ZE C200HE CPUjj E ZE...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ......
Страница 23: ......
Страница 63: ......
Страница 109: ......
Страница 127: ......
Страница 212: ...Appendix B Specifications 197 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 227: ......
Страница 233: ......