![Omron C200HE-CPU -Z Series Скачать руководство пользователя страница 183](http://html1.mh-extra.com/html/omron/c200he-cpu-z-series/c200he-cpu-z-series_installation-manual_742479183.webp)
Appendix B
Specifications
168
Transistor Output Unit C200H-OD21B (32 Points)
(Load Short-circuit Protection Provided)
Max. Switching Current
0.5 A 24 VDC
+10%
/
–15%
(5 A/Unit)
Min. Switching Current
None
Leakage Current
0.1 mA max.
Residual Voltage
0.8 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
32 (32 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuses
One 7 A fuse (1 fuse/common)
The fuses are not user-replacable.
Power for External Supply
160 mA 24 VDC
+10%
/
–15%
min.
(5 mA
×
number of ON pts)
Weight
180 g max.
Alarm Indicator
Lamp F lights (unless fuse is broken).
Load Short-circuit Prevention
(see note 1)
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
Dimensions
C-shape
Note When the short-circuit/overload protection is activated for a contact point, the output for that point is turned
OFF. At the same time, lamp “F” lights up, and the alarm from AR0205 to AR0214 corresponding to the I/O
number turns ON. After the cause of the error has been removed, the alarm will be cleared automatically
when the internal temperature of the element drops.
Circuit Configuration
Output LED
indicator
Internal circuit
Alarm
LED
indi-
cator
Output LED
indicator
to
to
to
to
0 V
0 V
0 V
0 V
Short-circuit
protection
circuit
Short-circuit
protection
circuit
Содержание C200HE-CPU -Z Series
Страница 1: ...Cat No W302 E1 09 Programmable Controllers C200HX CPUjj E ZE C200HG CPUjj E ZE C200HE CPUjj E ZE...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ......
Страница 23: ......
Страница 63: ......
Страница 109: ......
Страница 127: ......
Страница 212: ...Appendix B Specifications 197 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 227: ......
Страница 233: ......