Appendix B
Specifications
210
Transmission distance: 500 m max.
Transmission cable: VCTF 0.75 mm
2
or higher
B7A Link Terminal
B7A Link Terminal
12 to 24 VDC
B7A Interface Unit
12 to 24 VDC
12 to 24 VDC
Separate Power Supplies
High-speed Transmission Delays (3 ms): Shielded Cable
Transmission distance: 50 m max.
Shielded cable: 0.75 mm
2
or higher
B7A Link Terminal
B7A Link Terminal
24 VDC
±
10%
B7A Interface Unit
Shielded cable: 0.75 mm
2
or higher
GND
GND
Common Power Supply
Transmission distance: 100 m max.
Shielded cable: 0.75 mm
2
or higher
B7A Link Terminal
B7A Link Terminal
12 to 24 VDC
B7A Interface Unit
Shielded cable: 0.75 mm
2
or higher
GND
GND
12 to 24 VDC
12 to 24 VDC
Separate Power Supplies
Note 1. We recommend grounding the shielded cable.
2. If shielded cable is not used, the maximum transmission distance is 10 m regardless of whether a com-
mon or separate power supplies are used. (Use 0.75 mm
2
or higher VCTF cable.)
3. To prevent noise on the transmission cable, do not lay it near power cables or high-voltage lines.
Содержание C200HE-CPU -Z Series
Страница 1: ...Cat No W302 E1 09 Programmable Controllers C200HX CPUjj E ZE C200HG CPUjj E ZE C200HE CPUjj E ZE...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ......
Страница 23: ......
Страница 63: ......
Страница 109: ......
Страница 127: ......
Страница 212: ...Appendix B Specifications 197 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 227: ......
Страница 233: ......