10-1 Specifications
BU150R
99
10
10 References
10-1 Specifications
Method
Operation method
Full-time inverter supply method (Automatic Switching)
Cooling method
Forced air cooling
Input
Rated input voltage
AC100V/110V/115V/120V
Input voltage range
AC70V
±
2V
~
146V
±
2V (with less than 90% connection
load)
Frequency
50/60Hz
±
5.5Hz
Input Maximum current *1
15A
Phase
Single-phase, two-wire (grounded)
Input protection
Non Fuse Breaker (20A)
Input plug shape
NEMA 5-15P (*4)
Output
Rated output capacity
1500VA/1200W (*4)
Voltage
Commercial
Operation and
Backup operation
100V mode: 100VAC
±
2%, 110V mode: 110VAC
±
2%
115V mode: 115VAC
±
2%, 120V mode: 120VAC
±
2%
Frequency
Commercial operation: Synchronized with input frequency
Backup operation: 50/60Hz
±
0.5%
Wavef
orm
Commercial operation Sine wave
Backup operation
Sine wave
Distortion rate
6% max. (Rectified load, at rated output)
3% max. (Resistance load, at rated output)
Phase
Single-phase, two-wire (grounded)
Output receptacle
NEMA 5-15R x 6
Battery
Type
Sealed lead battery
Voltage / Capacity x Quantity 12V/9Ah
×
4
Backup time
(25°C, initial characteristics)
10min. (900W)
6min. (1200W)
Charging time
8 hours
Battery
life
Expected life: 5
years
Expected life: 5 years
Содержание BU150R
Страница 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Страница 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Страница 101: ...10 References 10 2 Dimensions BU150R 101 10 10 2 Dimensions Unit mm Tolerance 2mm BU150R 438 480 87...
Страница 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Страница 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Страница 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...