4 Maintenance and Inspection
4-2 Replacing the battery
BU150R
65
4
4-2 Replacing the battery
The battery can be replaced while the unit is stopped (power supply output stopped).
Refer to the below-shown reference data "10-3 Battery life" for the details about the life of
the battery.
Caution (for battery replacement)
Risk of explosion if battery is replaced by an incorrect type.
When replacing batteries replace with the same type and
number of batteries or battery packs.
Notes
Be sure to reset the battery life counter after replacing the battery.
Press and hold the "Buzzer Pause/Test" switch of the UPS for 10 seconds or longer to
reset the battery life counter. Resetting is complete when "bJ" is displayed.
* Reset the battery life counter with the "AC input" plug connected.
・
Stopping ("Power" switch OFF): When the beeper becomes a sustained beep,
release the switch.
・
In Commercial Power Mode ("Power" switch ON): When the beeper changes from
intermittent beeps to a sustained beep, release the switch.
If you do not reset the battery life counter, a battery deterioration alarm may occur
faster than the expected battery life.
When the unit is used in compliance with UL standards or CE marking, battery
replacement should be performed or supervised by personnel familiar with the danger of
batteries and the required precautions.
If an input power supply error such as a power failure occurs when replacing the battery
while in operation, backup cannot be performed and output stops.
Do not replace the battery while the UPS is operating in backup mode. Output will stop.
Write the battery replacement date in the attached battery replacement date sticker
provided with the replacement battery pack, and attach the sticker to the UPS.
* We are collecting replaced and unneeded batteries at no cost provided that the costs
of shipment to us are borne by the customers. For details, see the attachment "
Guidance for replace service " provided with the replacement battery pack.
Additional Information
When the battery replacement LED lights up/blinks and beeper sounds, press the "Buzzer
Pause/Test" switch for 0.5 seconds to stop the beeper. (Lighting/blinking of "battery
replacement" LED does not disappear.)
Содержание BU150R
Страница 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Страница 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Страница 101: ...10 References 10 2 Dimensions BU150R 101 10 10 2 Dimensions Unit mm Tolerance 2mm BU150R 438 480 87...
Страница 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Страница 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Страница 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...