The operation level is lowered according to the following calcula-
tion.
OP1= OP2 x VF/OF
OP1: Stall prevention operation level during acceleration in the
constant power output area
OP2: Stall prevention operation level during acceleration (No. 30)
VF: Maximum voltage frequency (No. 04)
OF: Output frequency
2-8-13 Full-range Automatic Torque Boost
Item name
Constant to be set
Factory preset
Torque compensation gain
No. 29
1.0
Automatic control of V/f ratio according to the load torque ensures
tripless operation and optimum output current. Normally, no
adjustment is necessary. Use this function especially when motor
capacity is smaller than Inverter capacity and torque is required.
100%
Torque
increase
Torque
decrease
Normal frequency
Output voltage
Description of Functions and Constants