41
Third Functions (Constant Nos. 30 to 49)
Function
No.
Name
Description
Initial
setting
User
set
values
See
Page
Stall Prevention
30
Level of stall
preventive
operation
during
acceleration
Setting unit: 1%, setting range 30% to
200%
Note: Stall prevention is not performed
during acceleration when 200% is set.
170%
51
31
Level of stall
preventive
operation
during run-
ning
Setting unit: 1%, setting range 30% to
200%
Note: Stall prevention is not performed
during run when 200% is set.
160%
Multi-
func-
tion
selec-
tion
Contact
input
signal
32
Multifunction
input selec-
tion 1 (termi-
nal 4 func-
tion selec-
tion)
0: FWD/REV run command
(3-WIRE sequence selection)
1: External fault (NO contact input)
2: External fault (NC contact input)
3: Multi-step speed reference 1
4:Multi-step speed reference 2
5: JOG command
6: Accel/decel time select
7: External baseblock (NO contact input
8: External baseblock (NC contact input)
9: Speed search from max. frequency
10: Speed search from set frequency
11: Accel/decel prohibit
12: Local/Remote operation
1
53
33
Multifunction
input selec-
tion 2 (termi-
nal 5 func-
tion selec-
tion)
1: External fault (NO contact input)
2: External fault (NC contact input)
3: Multi-step speed reference 1
4:Multi-step speed reference 2
5: JOG command
6: Accel/decel time select
7: External baseblock (NO contact input
8: External baseblock (NC contact input)
9: Speed search from max. frequency
10: Speed search from set frequency
11: Accel/decel prohibit
12: Local/Remote operation
14: UP/DOWN command
3
Function/Constant List
Section 2-7