12
Circuit
Wire type
Wire size
Terminal
screw
Terminal symbol
Inverter
capacity
Model
3G3XV
Circuit
Wire type
mm
2
AWG
Terminal
screw
Terminal symbol
Inverter
capacity
Model
3G3XV
Main
circuit
AB015
2.5 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
Power cable:
600 V
G (E)
14-10
2 to 5.5
600
vinyl-sheathed
lead or
AB022
4.2 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M5
12-8
3.5 to 8
lead or
equivalent
G (E)
14-8
2 to 8
AB037
6.7 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M5
10-8
5.5 to 8
G (E)
14-8
2 to 8
Control
circuit
Common
to all
–––
1 to 14,
FLT-A, FLT-B, FLT-C
M3.5
20-14
0.5 to 2
Shielded lead
or equivalent
Models
G (E)
q
400-V-class 3-phase Input Series:
Circuit
Model
3G3XV
Inverter
i
Terminal symbol
Terminal
Wire size
Wire type
3G3XV
capacity
y
screw
AWG
mm
2
yp
Main
circuit
A4002
0.8 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
Power cable:
600 V
G (E)
14-10
2 to 5.5
600
vinyl-sheathed
lead or
A4004
1.2 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
lead or
equivalent
G (E)
14-10
2 to 5.5
A4007
2.0 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
A4015
3.0 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
A4022
3.7 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
A4037
6.1 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
Control
circuit
Common
to all
–––
1 to 14,
FLT-A, FLT-B, FLT-C
M3.5
20-14
0.5 to 2
Shielded lead
or equivalent
Models
G (E)
q
Wiring
Section 1-4