Wire Sizes and Types
200-V-class 3-phase Input Series:
Circuit
Model
3G3XV
Inverter
i
Terminal symbol
Terminal
Wire size
Wire type
3G3XV
capacity
y
screw
AWG
mm
2
yp
Main
circuit
A2001
0.3 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
Power cable:
600 V
G (E)
14-10
2 to 5.5
600
vinyl-sheathed
lead or
A2002
0.6 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
lead or
equivalent
G (E)
14-10
2 to 5.5
A2004
1.1 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
A2007
1.9 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
A2015
2.5 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
12-10
3.5 to 5.5
G (E)
14-10
2 to 5.5
A2022
4.2 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
12-10
3.5 to 5.5
G (E)
14-10
2 to 5.5
A2037
6.7 kVA
L1 (R), L2 (S), L3 (T), B1/
⊕
,
B2, T1 (U), T2 (V), T3 (W)
M4
12-10
3.5 to 5.5
G (E)
14-10
2 to 5.5
Control
circuit
Common
to all
–––
1 to 14,
FLT-A, FLT-B, FLT-C
M3.5
20-14
0.5 to 2
Shielded lead
or equivalent
Models
G (E)
q
200-V-class Single-phase Input Series:
Circuit
Model
3G3XV
Inverter
i
Terminal symbol
Terminal
Wire size
Wire type
3G3XV
capacity
y
screw
AWG
mm
2
yp
Main
circuit
AB001
0.3 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
Power cable:
600 V
G (E)
14-10
2 to 5.5
600
vinyl-sheathed
lead or
AB002
0.6 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
lead or
equivalent
G (E)
14-10
2 to 5.5
AB004
1.1 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
AB007
1.9 kVA
L1 (R), L2 (S), B1/
⊕
, B2, T1
(U), T2 (V), T3 (W)
M4
14-10
2 to 5.5
G (E)
14-10
2 to 5.5
Wiring
Section 1-4