5-1
5-1 Operation Selection During Option Error
5
Maintenance Operations
5Maintenance Operations
5-1 Operation Selection During Option Error
You can select whether to trip the Inverter or continue operation ignoring an error when the optional
PG Board causes an error.
Note:Even if 01 has been selected in operation selection at option error, the Inverter trips when an
encoder disconnection error (E60, E70) or
3G3AX-PG
connection error (E69, E79) occurs.
Refer to "2-6 Switch Settings"(page 2-8).
Parameter No.
Function name
Data
Default
setting
Changes dur-
ing operation
Unit
P001
Operation selection at option
1 error
00: Trip
01: Continues operation
00
×
−
P002
Operation selection at option
2 error
00: Trip
01: Continues operation
00
×
−
Содержание 3G3AX-PG
Страница 1: ...Cat No I564 E1 01 USER S MANUAL 3G3AX PG Encorder Feedback Board ...
Страница 2: ......
Страница 14: ...12 Contents ...
Страница 15: ...Chapter 1 Overview 1 1 Overview 1 1 ...
Страница 27: ...Chapter 3 Operation 3 1 Related Parameters 3 1 3 2 Precautions for Operation 3 8 ...
Страница 65: ...Chapter 6 Specifications 6 1 Product Specifications 6 1 ...
Страница 67: ......