4-23
4-4 Absolute Position/High-resolution Absolute Position Control Modes
4
Functions
Pulse Train Frequency Input
This function allows you to use a pulse train input to the SAP-SAN terminals on the PG Board as
frequency reference or PID feedback value in each control mode.
(This function can be used in all control modes.)
Set the input frequency at the maximum frequency in pulse train frequency scale P055.
The analog input start/end function cannot be used. To limit the input frequency, use pulse train fre-
quency bias amount P057 and pulse train frequency limit P058.
Pulse train frequency processing block
Note: Set the SWENC switch on the PG Board to “OFF: encoder disconnection detection
disabled”.
Parameter No.
Function name
Data
Default
setting
Unit
P055
Pulse train frequency scale
1.0 to 50.0: Set the input frequency at the
maximum frequency.
25.0
kHz
P056
Pulse train frequency filter
time constant
0.01 to 2.00: Set a filter time constant for
pulse train input.
0.10
s
P057
Pulse train frequency bias
amount
−
100. to +100.
0.
%
P058
Pulse train frequency limit
0. to 100.
100.
%
A001
Frequency reference
selection
06: Pulse train frequency
02
−
A076
PID feedback selection
03: Pulse train frequency
00
A141
Operation frequency input
A setting
07: Pulse train frequency
02
A142
Operation frequency input
B setting
07: Pulse train frequency
03
Frequency
measurement
Hz
%
Frequency scale (P055)
(1.0 to 50.0 kHz)
First-order lag filter (P056)
1
1+sT
Bias/Limit
Limit
Bias
%
Hz
Maximum
frequency
(A004)
Frequency
reference
Содержание 3G3AX-PG
Страница 1: ...Cat No I564 E1 01 USER S MANUAL 3G3AX PG Encorder Feedback Board ...
Страница 2: ......
Страница 14: ...12 Contents ...
Страница 15: ...Chapter 1 Overview 1 1 Overview 1 1 ...
Страница 27: ...Chapter 3 Operation 3 1 Related Parameters 3 1 3 2 Precautions for Operation 3 8 ...
Страница 65: ...Chapter 6 Specifications 6 1 Product Specifications 6 1 ...
Страница 67: ......