Maxiflex P3 PAC User Manual
72
-© Omniflex
UMM126XR18.pdf
3. When setting up the Module List in the Remote Rack remember to set the
Network Offset of the Conet/s Link to
156
as shown below. This will allow you
access to the Remote Rack through the Programming Port of the Controller.
11.7.1 Check the Status of installed modules
Once the I/O Module List has been set, you can check if the modules currently installed
match this list.
To check whether the Maxiflex modules actually installed on your Maxiflex Racks match
your configured I/O Module List, follow this procedure:
1.
Change to the “I/O Module Status” Group:
2. The eight
“I/O Module List Status” registers identify any mismatches between the
four I/O Module Lists and the actual modules installed in each rack of the system.
The eight
“I/O Module User Prog.Status” registers identify the mismatches between
the I/O module configuration as set within an IEC61131 program, if any, running on
the CPU.
Each bit set to 1 indicates a mismatch in the corresponding module Slot. The Least
Significant (Right Most) Bit, Bit 0, represents the module in the PSU Slot; the next
bit, Bit 1, represents the module in I/O Slot 1; up to the Most Significant Bit (Left
Most) Bit 15 in the register represents the module in I/O Slot 15.
If all modules match, (=0), then the I/O Module List Status and the I/O User Prog
Status bits in the overall system status register will be set to 0 (shown as
“OK”
below). If any of the modules do not match, then this bit will be set to 1.