Maxiflex P3 PAC User Manual
71
-© Omniflex
UMM126XR18.pdf
2. In a configuration file on your hard drive once you save your configuration to file from
Omniset.
3. In your target P3 once you download the configuration to the target P3 CPU.
If you are configuring on-line (i.e. connected to the target P3 CPU), then you can synchronise
the target P3 CPU and Omniset so that any changes you make to your configuration in
Omniset are automatically downloaded to the target P3 CPU the moment you change them.
To synchronise Omniset with your target P3, you must perform one of the following actions:
1. Read All Groups from your target P3 into Omniset.
2. Write All Groups from Omniset to your target P3.
3. Verify All Groups to confirm that the configuration in your P3 target matches the
configuration in the configuration file loaded in Omniset.
At the end any of these actions, you will be given the opportunity to elect to stay in
Synchronism with your target P3 CPU. This is recommended if you will be changing quite a
number of settings.
All future configuration instructions in this chapter assume that your Omniset is synchronised
with your target P3 CPU.
11.6 Configuring the Programming Port
The P3 CPU programming port is dedicated to the Programming and Configuration of the P3
CPU and requires no configuration.
1
11.7 Configuring the I/O Module List using Omniset
To configure the P3 I/O Module List, follow this procedure:
1. Select the
“Modules” Group under “Configuration”.
2. Select the required module type in each Slot in the Rack.
1
This port is permanently configured for the Conet/s protocol (operating at 19,200 baud, 8 data bits, no parity,
and 1 stop bit.)