7.9 M1330A
– 8DI8RO 8way Digital Input /8 way Relay Output Module
DIGITAL INPUT DATA SPACE
DIT (Offset)
Digital Inputs 1-8
where individual inputs are allocated as follows:
0
Input 1 = Bit 0 (LSB)
Input 2 = Bit 1
Input 3 = Bit 2
Input 4 = Bit 3
Input 5 = Bit 4
Input 6 = Bit 5
Input 7 = Bit 6
Input 8 = Bit 7
Bits 9 to 16 will read as 0
DIGITAL OUTPUT DATA SPACE
DIT (Offset)
Digital Outputs 1-8
where individual inputs are allocated as follows:
1
Output 1 = Bit 0 (LSB)
Output 2 = Bit 1
Output 3 = Bit 2
Output 4 = Bit 3
Output 5 = Bit 4
Output 6 = Bit 5
Output 7 = Bit 6
Output 8 = Bit 7
Bits 9 to 16 are unused.
All other Data Spaces are unused by this module
Example:
Input 5 of an M1330A module installed in Local Slot 3 can be read from DIT Address 5012,
Bit 4
Output 5 of an M1330A module installed in Local Slot 3 can be energised by writing a ‘1’ to
Bit 4 of DIT Register 4513
7.10 M1341B
– 16DO – 16way Digital Output Module
DIGITAL OUTPUT DATA SPACE
DIT (Offset)
Digital Outputs 1-16
where individual outputs are allocated as follows:
0
Output 1 = Bit 0 (LSB)
Output 2 = Bit 1
Output 3 = Bit 2
Output 4 = Bit 3
Output 5 = Bit 4
Output 6 = Bit 5
Output 7 = Bit 6
Output 8 = Bit 7
Output 9 = Bit 8
Output 10 = Bit 9
Output 11 = Bit 10
Output 12 = Bit 11
Output 13 = Bit 12
Output 14 = Bit 13
Output 15 = Bit 14
Output 16 = Bit 15 (MSB)
All other Data Spaces are unused by this module
Example:
Output 3 of an M1341B module installed in Slot 4 can be energised by writing to DIT Address
4516, Bit 2