Maxiflex P3 PAC User Manual
68
-© Omniflex
UMM126XR18.pdf
8
1 2 3 4 5 6 7
ON
8
1 2 3 4 5 6 7
ON
Communications Protocol
Conet Address switch setting
Conet (Normal mode):
Baud rate: 62,500 baud
Switches 1-7: Conet ID
(Set in binary
Switch 1 = LSB
Switch 7 = MSB)
Switch 8: Baud Rate
Switch 8 OFF = 62.5 kBaud
[Switch shown set to Address 2, Normal baud rate]
Conet (Slow mode):
Baud rate: 7,800 baud
Switches 1-7: Conet ID
Switch 8: Baud
Switch 8 ON = 7.8 kBaud
[Switch shown set to Address 2, Slow baud rate]
Table 11.2: Conet Port Address switch settings (M1261D P3c)
Each node on the Conet/c network should be allocated a unique address in sequence,
starting at 1.
Please refer to the Conet Installation Guide and Conet Protocol Datasheet for more
information on the CONET network.
11.4 Preparing the Omniset configuration software to configure the P3 CPU
Most of the features available on the P3 CPU can be configured by writing to Registers in the
Data Interchange Table (DIT) of the CPU. (This excludes IEC61131 programming that is
done using the Omniflex ISaGraf Programming Workbench.)
The recommended method for configuring a P3 CPU is to use the Microsoft
Windows95/98/NT/2000/XP/7 compatible Omniset software configuration utility.
It is also possible to configure a P3 CPU through any of its communications ports that have
access to the DIT, using any software capable of writing to the DIT registers of the CPU.
The full DIT register layout is available separately from Omniflex Technical Support, or it can
be found in the Product Template File, viewed with Omniset.
11.4.1 Omniset
The Omniset configuration utility is available free of charge for the purpose of configuring a
wide range of OMNIFLEX products, including this range of CPU’s. A Template File
compatible with the product is required, and is normally supplied with Omniset. Check for the
latest available versions on the OMNIFLEX web site (
www.omniflex.com
) or with the
Omniflex technical support department on
.
Using Omniset, you can configure the P3 CPU locally through the programming port. If you
wish to configure the P3 CPU remotely over a network, then you must purchase Omniset
Pro, the full featured version of this software.
11.4.2 Omniset Pro
1. The Omniset Pro software utility is an enhanced version of Omniset, and allows
configuration of the P3 CPU remotely over a network. Omniset Pro also provides the
ability to edit and create custom Template files.
2. For Remote I/O access you will need to configure the Network Offset of the Conet/s Link
in the Conet Server. The Network Offset must be set to
140
as shown in the screen grab