Maxiflex P3 PAC User Manual
106
-© Omniflex
UMM126XR18.pdf
14.5 Step 5: Configure Primary Controller
Plug a programming cable into the primary controller and configure the Primary Controller
and Remote I/O using Omniset, as if it were the only controller in the system. See chapter 11
for full instructions on configuring the primary controller CPU.
If you require any user data DIT to be synchronised between primary and secondary
controllers, then you can organise this data in the Data Interchange Table (DIT) into up to
three blocks of any length. You then configure the address and size of these Sync Blocks in
the primary controller as shown below.
Figure 14.1: Setting the Sync Parameters in Omniset
The system change-over time settings are also in this configuration group. Change these
timers from their default settings if required.
Once the Primary Controller is fully configured, the RUN LED should be on steady indicating
that it is the controller in control.
14.6 Step 6: Test I/O Access from Primary Controller
From Omniset, view the status of I/O from every I/O rack ensuring that the status is properly
indicated in the relevant Omniset group