OMICRON
21
Technical data
4.4
Outputs
4.4.1
General generator outputs
All voltages and current generators can independently be configured with respect to amplitude, phase
angle, and frequency.
All outputs are monitored. Overload conditions prompt a notification in the control software.
General generator outputs data (analog current and voltage outputs)
Frequency ranges
1
1. For injections longer than 1 minute, the maximum fundamental frequency is limited to 587 Hz to comply with international trade
restrictions for frequency-controlled signal generators. For other options, please contact OMICRON Support.
Sinusoidal signals
2
2. Amplitude derating for current outputs at frequencies above 380 Hz.
10 … 599 Hz
Frequency resolution
(signal generation)
<5 μHz
Phase range
ϕ
–360° ... +360°
Phase resolution
0.001°
Phase error
→ section 4.4.2 "Current outputs" on page 22
→ section 4.4.3 "Voltage outputs" on page 25
Amplitude temperature drift
0.0025 %/°C
CURRENT OUTPUT
3 × 32 A
RMS
1
2
3
N
1
2
3
N
VOLTAGE OUTPUT
3 × 300 V
RMS