12 |
P a g e
END DEVICE READINGS AND CONFIGURATION
This section details how to view, log and chart data received from End Devices. Turn on and
configure any End Devices now. Confirm that all End Devices are set to the same Network ID
as the desired ZW-REC. Also ensure each End Device has a different Device ID selected. If an
End Device is running, it needs to be reset after changes to the Device ID or Network ID.
Power on all End Devices now. If existing End Devices are running they may need to be reset
now.
Please refer to the End Device user manual for detailed instructions on setting Network IDs
and Device IDs.
The ZW-REC can display a NID chart to help configure zSeries and zwSeries End
Devices. Refer to
Section 5.1
for more information.
4.1 End Device Readings Page
When logging into the ZW-REC the End Device Readings page is displayed. The readings page
shows the current sensor data from all connected End Devices. When an End Device turns on
it enters active scan mode and search for a receiver. When the ZW-REC is found the Blue
Wireless Link Indicator on the End Device flashes once and turns off. The Link Indicator flashes
again each time a reading is transmitted. Once an End Device finishes connecting to the ZW-
REC it is automatically added to the reading page.
The readings page shows the End Device ID, Name and Status followed by readings from any
connected sensors. End Device Status will change from Good to Lost if an End Device misses
three transmissions in a row.
The Sequence Number is transmitted by the End Device and incremented with each
transmission. An increasing sequence number shows that the web page is getting fresh data
Figure 7. End Device Readings (Populated)