number of meter stations and cable length can further be increased. The cable wires are to be connected to
terminals 6 and 7.
The flow meter found at the end of the communication network shall be provided with jumper W1 with
a terminal resistor 120 R. Jumper W1 is located on the terminal board FNS5 between the terminal strip and
lightning arrestor
flow meter 1 flow meter 2
flow meter 3 flow meter 4
Connection of flow meters to an RS 485 communication line
Communication
Communication consists of individual data packets. To ensure correct function of a communication network,
each station must have a different address. On delivery, all induction flow meters will have the following
setting of communication parameters:
Address 1, Group 1, Speed 9600Bd, Parity SL.
Communication uses the Floset 2.0 program package.
The communication protocol is not included in this brochure; it can be obtained from the meter manufacturer
on request.
Menu:
Serial line, depress
Address
Group
Baud rate
Parity
The two-line display will always show two of the menu items. To page through the menu, use push buttons
(direction upwards) and (downwards). Select the desired item and depress .
Menu:
Serial line, depress / Address, depress
The display will read “Address xxx”. Replace “xxx” by a number from 1 to 255, being the meter address.
Depress . The display will show the message “Value entered Press any key”. Press any key, preferably
. This command will take you back to the Serial Line menu.
Menu:
Serial line, depress / Group, depress
The display will read “Group xxx”. Replace “xxx” by a number from 1 to 255, being the designation of a group
of induction meters. Depress . The display will show the message “Value entered Press any key”. Press
any key, preferably . This command will take you back to the Serial Line menu.