Page 13
2.1.3.
LED Module
The status of each channel is indicated by LEDs. Each detector can be
connected to any channel.
Operation of the buttons for the respective channels displays additional
information about the connected detector on the LCD module and triggers
further channel functions such as alarm suspension, operational test,
channel disconnection and calibration mode.
The LED module consists of an LED panel for 16 channels and one or
two PCBs for eight channels each.
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
2.1.4.
Basic relay (RBM) and Extension relay module (REM)
A RBM has eight relays and can be extended by eight relays with a
pluggable REM.
Redundant triggering of the relays is done via two 8 bit micro controllers.
Free parameter setting of the relays with the help of software
ConfigPro
meets all individual requirements:
Open and closed circuit operation
Grouping
AND / OR logic operation
Voting
ADVANCED relay functions
Time-delay and slow Release
Buzzer relay function
Relay reproduction