Page 52
7.6.
Analog output module (AAM)
Different addresses between 1 and 8 have to be allocated to the AAMs with the
help of the fitted rotary switch.
Each output has a pertaining jumper by which 0-10 V or 4-20 mA can be
selected.
left position
:
0
–
10 V
right position
:
4
–
20 mA
The last output module (whether it is a relay or analog output module) has to
form a bus end for both signal buses (redundancy). This is done with the two
jumpers on the upper right-hand side.
left position
:
end of bus
right position
:
further output modules
Module size: 160 x 90 x 50 mm