INSTRUCTIONS Commissioning guide for AHC-3000
14.7 Configuring the heating
Here, you now select the after heating coil from among
these possibilities:
• No after heating coil
• Water heating coil*
• Electro heating coil
*= factory setting
The AHU must be in operational mode “Service stop”
_
from main screen menu, in order to activate the new
updated software.
Note!
When “Water heating” is selected, the digital output for circulation pump and frost protection
of the heating battery is automatic selected. The default setting for frost protection is through the
temperature sensor on the return water.
The return water sensor can be deselected under the menu “Temperature”.
Frost protection settings are made on the “Commissioning” menu.
Frost protection is also available through a capillary tube alarm (frost thermostat). To set frost
protection using a frost thermostat, select this under “Digital inputs”.
Warning:
If the frost protection sensor is deselected and no capillary tube alarm (frost thermostat) is
configured, there is a risk of damaging the water heating battery.