INSTRUCTIONS Commissioning guide for AHC-3000
20.3 Heating coil settings (Electric coil 1)
Available settings
Setpoint
√ Current setpoint for the current temperature control mode
√ Setting range: 5.0–40.0°C
Current
√ Current supply air temperature
Flow supply
√ Current supply air flow (m
3
/h)
Heating
√ Current status value on the heating output (range 0–100%)
Reduced heating
√ Current status on the reduced heating function.
√ “YES”: If the heating has been reduced because the supply air flow is lower than the set value
√ “NO”: If the heating is not reduced
0% heat power
√ Fan-speed setpoint (% of the max. AHU volume) for supply air, the heating must be off (0%).
√ If the air flow is below the value of this setpoint, the heat power is forced “Off”
100% heat power
√ Setpoint for the minimum fan speed (% of the max. AHU volume) of the supply air, the heating
is allowed to be 100% on.
√ If the air flow is below the value of this setpoint, the heat power is reduced.