INSTRUCTIONS Commissioning guide for AHC-3000
15. Autoconfiguring the AHU field components
This shows the autoconfigured Air Handling Unit field options
•
Duct
pressure
•
Filter
pressure
•
Room
temperature
•
Timer
button
•
Remote
setpoint
•
CO2
control
•
VOC
control
•
Humidity
All field options, functions and components are auto selected when detected by a sensor.
This means that as soon as a pressure transmitter, VOC sensor, humidity sensor or HMI-20T room
display has been detected on the Modbus, the sensor and the including function will be activated.
Example 1:
An HMI-20T is connected to the Modbus port via the RJ12 port marked “A”.
As soon as the HMI-20T is detected on the Modbus, the functions:
√
Room
temperature
√
Timer
button
√
Remote
set-point
- will automatically be selected
Example 2:
An VTH-6202 VOC sensor is connected to the Modbus port via the RJ12 port marked “B”.
As soon as the VTH-6202 is detected on the Modbus, the functions:
•
VOC
control
- will automatically be selected