INSTRUCTIONS Commissioning guide for AHC-3000
19. Control settings
19.1 Fan control mode: Constant pressure
• Select the fan control mode: Constant pressure
– the procedure is the same for the supply and exhaust air fans.
√
Low speed
(Pressure setpoint)
√
Medium speed
(Pressure setpoint)
√
High speed
(Pressure setpoint)
√
Airflow
(current value)
√
Min. air volume
(min. flow setpoint)
√
Max. air volume
(max. flow setpoint)
√
Fan pressure
(current value)
√
Supply air duct
(current value)
√
Energy consumption
(current value, only OJ-DV)
√
K-factor
(l/s)
√
Delayed start
(time setpoint)
Setpoints can be changed by touching the blue setpoint values and
changing the value via the setpoint keyboard. Save & exit with “OK”