INSTRUCTIONS Commissioning guide for AHC-3000
Reset alarms:
Clear Alarms will clear all active alarms.
After activating “Clear alarms”, any alarms still active in the system will be re-triggered and shortly
after show up again in the alarm overview.
Up to 16 active and logged alarms will be listed.
Alarm details and description:
Select the actual alarm (*1)
Latest cleared alarms will be listed in the
alarm log: “Log date & alarm number” (*2)
13. Communication set-up
The AHC-3000 can communicate on:
• a BMS system via Modbus TCP/IP and Modbus RTU (see 13.1)
• Directly connected to a computer via a LAN cable (RJ45) (see 13.2)
The AHC-3000 can also be connected to the OJ Cloud via the internet or a mobile app via Bluetooth
13.1 Modbus TCP/IP – DHCP
If the AHC-3000 is connected to a local area network (LAN) with a DHCP server, select “
Dynamic
IP
” under the menu “
Static/Dynamic IP
”
The DHCP server will automatically set all the necessary information in the AHC-3000, including: IP
address, Netmask, Gateway and DNS.
As soon as the AHC-3000 receives an IP address, Netmask, Gateway and DNS from the DHCP
server, this information will be found in the menu below.