Ignition
,
200, 250, 300, 400, 500, 600, 700, 800, 900, 999
On full capacity curve point:
1. Adjust the burner´s capacity. Note the ratio control.
2. Check combustion values with flue gas analysis.
3. Check flame combustion.
Measure fuel consumption on every adjusting point so that the set of
curves correspond to the genuine load situation.
Check combustion values of ignition capacity with flue gas analysis.
4.18 Setting ratio curve, oil (2-stage)
Creating 2-stage operation curve points
1
1-stage point (same as the ignition point)
1 > 2
2-stage valve opening point when shifting from
1-stage to 2-stage
1 < 2
2-stage valve closing point when shifting from 2-
stage to 1-stage
2
2-stage point
Point 1 > 2 set value is recommended to be set bigger than point 1 < 2.
Set the ratio curve in the control panel menu
3400 edit2 ver. 1
1
fuel (set of curves)
2
set condition
3
level 2 password (burner manufacturer)
4
menu number
5
pillar display: capacity-%
6
O2: residual oxygen -%
7
actuators: CH1, CH2, CH3
8
S-row: set points/channel
M5164 1640EN