Overlying oil tank
Underlying oil tank
SUNTEC AJ4 (150 l/h)
H (ft)
ø 0.39″ ø 0.47″ ø 0.55″ ø 0.63″
0
0.43
0.94
1.81
3.15
1
0.47
1.06
2.01
3.54
3
0.55
1.18
2.24
3.90
6
0.67
1.42
2.68
4.65
9
0.79
1.65
3.11
5.35
13
0.87
1.89
3.54
6.10
2850 rpm, 20 mm²/s (cSt)
D max. = 49 ft
(D-H) max. = 14 ft
SUNTEC AJ4 (150 l/h)
H (ft)
ø 0.39″ ø 0.47″ ø 0.55″ ø 0.63″
0
0.43
0.94
1.81
3.15
1
0.35
0.83
1.61
2.80
3
0.31
0.71
1.38
2.40
6
0.20
0.47
0.94
1.65
9
0.08
0.24
0.51
0.94
13
0
0
0.08
0.20
2850 rpm, 20 mm²/s (cSt)
H max. = 14 ft
SUNTEC AJ6 (250 l/h)
H (ft)
ø 0.39″ ø 0.47″ ø 0.55″ ø 0.63″
0
0.20
0.51
1.06
1.85
0,.5
0.24
0.59
1.18
2.05
1.0
0.28
0.67
1.30
2.28
2.0
0.35
0.83
1.57
2.76
3.0
0.39
0.94
1.85
3.15
4.0
0.47
1.10
2.09
3.62
2850 rpm, 20 mm²/s (cSt)
D max. = 49 ft
(D-H) max. = 14 ft
SUNTEC AJ6 (250 l/h)
H (ft)
ø 0.39″ ø 0.47″ ø 0.55″ ø 0.63″
0
0.20
0.51
1.06
1.85
0.5
0.16
0.47
0.91
1.61
1.0
0.12
0.39
0.79
1.42
2.0
0.08
0.24
0.51
0.94
3.0
0
0.12
0.28
0.51
4.0
0
0
0
0.08
2850 rpm, 20 mm²/s (cSt)
H max. = 14 ft
3.10 Electrical connections
Connect burner according to the electrical diagrams delivered with burner.
Adhere to general and local standards and regulations as well as requirements set on
the connections of electrical equipment. Configure burner installation with a switch that
allows it to be disconnected from the low-voltage supply mains.
Grounding must be in order before commissioning burner.
See electrical diagram for maximum cable lengths.
Connection to power supply is implemented with two separate supply connections. The
supply of the control circuit of switching device directly to the burner switching base
and supply to the fan motor output are implemented according to the site. The motor
output is cabled both to the fan motor and control circuit to the burner wiring base.
Separate the base insulated wires of different voltage circuits from each other.
30 (95)
M5164 1640EN
Содержание GKP-50 MH
Страница 2: ......
Страница 21: ...3 3 Installing burner GKP 50 MH main dimensions D048897 ver 3 M5164 1640EN 19 95...
Страница 98: ...96 95 M5164 1640EN...
Страница 99: ......
Страница 100: ...Tarmontie 4 FI 15860 HOLLOLA FINLAND Tel 358 3 85 761 Fax 358 3 857 6239 Email info oilon com www oilon com...