5.4.10 Soft starter alarms
This view allows you to enable and disable alarms for the soft starter. The available
options are
Soft starter
and
Phase guard
.
5.4.11 Super heat circuit control: desuperheater control options
This view allows you to change the desuperheater pump’s settings.
Super heat circuit control ver. 1
The
Rinse interval
option determines the number of days after which the pump
completes a rinse cycle. The heat pump is rinsed during the first operating cycle of the
day.
The
Manual control
option allows you to specify a speed setting for the pump.
Factory defaults:
● ESi 6–9: 35%
● ESi 11–17: 40%
● EMi 22–43: 55%
● ELi 50: 75%
● ELi 90: 85%
5.4.12 Boiler maximum limits
This view allows you to set the minimum and maximum temperature setpoint for the
lower section of the storage tank.
5.4.13 Cooling (optional)
The cooling system has three control modes: Room temperature, External, and
Manual. These modes are used both in Free cooling and Flexible cooling.
M8010 2204EN
55 (75)