~ 20 ~
ET-485
NOVATEK-ELECTRO
Parameter
Min
– Max Factory setting
Description
Address
Bit rate in Modbus-
network, bit/sec
75 –
1,500,000
9,600
Used in case of data exchange between the units in Modbus-
network, the same value for all units in Modbus-network
534-535
Enable the odd-
even check
0-1
0
Used in case of data exchange between the units in Modbus-
network, the same value for all units in Modbus-network
0: unused, byte is completed with 2 stop bits
1: byte is completed with parity bit and 1 stop bit
536
Enable the odd-
even check
(to verify odds)
0-1
0
Used in case of data exchange between the units in Modbus-
network, if odd-even check is enabled. The same value for all
units in Modbus-network
0: Parity check
1: Imparity check
537
Response time
from Modbus RTU,
msec
0-60,000
200
Used in case of data transfer via the Modbus-network in RTU
mode. Waiting for a response is terminated if the first byte of the
response has not been received within the given time after
sending the request. The response is always expected longer
then time of silence between frames (time of silence depends
on the bit rate and shall be equal to the time required for
transmitting 3.5 bytes, or 1.75 msec for bit rate over 19,200
bits/sec).
538