~ 21 ~
NOVATEK-ELECTRO
ET-485
Parameter
Min
– Max Factory setting
Description
Address
Enable ASCII
exchange in
Modbus network
0-1
0
Exchange mode in Modbus-network, the same value for all
units in Modbus-network
0: RTU exchange mode (format: 1start bit, 8 data bits, 1 parity
bit or stop-bit or 1 stop bit – total 11 bits).
1: ASCII exchange mode (format: 1start bit, 7 data bits, 1 parity
bit or stop-bit or 1 stop bit – total 10 bits).
539
Response time for
subsequent
Modbus ASCII
character, msec
0-60,000
1000
Used in case of data transfer via the Modbus-network in ASCII
mode. Waiting for a response is terminated if the subsequent
byte of the response has not been received within the given
time, as indicated for the reception of response. Waiting time
shall not be less then time required for transmission of a single
character (depending on the bit rate).
540
Miscellaneous
Enable periodic
restart of the unit
0–1
0
0: periodic restart disabled
1: unit restarts at a specified interval of time
541
Unit restart
interval, min
5-7200
7200
Used if periodic restart of the unit is enabled
542
Password to enter
the setup mode
String of
characters
11111
Used to access the setup mode for Modbus TCP. Any string of
5 to 20 characters can be used as a password. It may not
contain spaces or special characters listed in quotes below:
«; : " < > * + = \ | / ? ,»
543-562