NOVATEK-ELECTRO

  ET-485

 

Parameter 

 Min 

– Max  Factory setting 

Description 

Address 

 

Enable 

replacement of 

non-active 

clients 

 

0-1 

 

0: Modbus TCP connection is maintained regardless of the 

time period between requests from the client 

1: if all connections to Modbus TCP are busy, the new client, 

requesting for a connection, can be connected instead of the 

client, who provided no requests over the longer then preset 

period 

 

528 

Maximum query 

timeout, sec 

 

0-9999 

 

90 

Used, if replacement of non-active clients is enabled 

 

529 

Enable the queue 

for the last busy 

Modbus TCP 

connection 

 

0-1 

 

0:  Modbus  TCP  connection  is  maintained  regardless  of  the 

connection hold time 

1:  if  all  connections  to  Modbus  TCP  are  busy,  the  new  client, 

requesting for a connection, can be connected instead of the last 

connected client, if the hold time is more than a preset time 

 

530 

The maximum hold 

time of the last 

connection to 

Modbus TCP, 

msec 

 

0-600,000 

 

60,000 

 

Used, if the queue is enabled for the last connection to Modbus 

TCP 

 

531–532 

Modbus network

 

Own Modbus-

identifier of the unit 

 

0-247 

 

111 

0:  unit  forwards  all  Modbus  TCP  requests  into  the  Modbus 

network, unit registers via Modbus TCP are unavailable 

1–247:  units  responds  to  Modbus  TCP  requests  bearing  the 

given  Modbus-identifier  without forwarding  them  to  the  Modbus 

network 

 

533 

Содержание ET- 485

Страница 1: ...NOVATEK ELECTRO LTD Intelligent Industrial Electronics Protocol converter Modbus RTU ASCII RS 485 to Modbus TCP Ethernet 485 USER MANUAL TECHNICAL DATA SHEET www novatek electro in...

Страница 2: ...ricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR THE EQUIPMENT YOURSELF It may contain energized parts DO NOT OPERATE THIS UNIT...

Страница 3: ...the 485 12 6 Operating the 485 13 6 1 General information 13 6 2 Operating 485 over the HTTP protocol 13 6 3 Operating 485 over the Modbus TCP protocol 13 7 Settings 14 7 1 General information 14 7 2...

Страница 4: ...is a routable protocol for transferring data over Ethernet It is a part of TCP IP and used for Internet IP address is a node address which is unique within a single network operating over the IP proto...

Страница 5: ...bus requests from the clients to the units in the Modbus network and returns their answers to the clients 485 has flexible addressing within the Ethernet network overloading MAC address static and dyn...

Страница 6: ...ted pair Supported Ethernet protocols Modbus TCP HTTP Maximum number of connections over the Modbus TCP protocol 11 Integrated servers Modbus server HTTP server Data Exchange Interface over the Modbus...

Страница 7: ...y II Rated insulation voltage V 450 Rated impulse withstand voltage kV 2 5 Operating position arbitrary Pollutants in the amount which is not to exceed the maximum permissible concentration none 2 2 O...

Страница 8: ...1 Structure 3 1 1 Design The unit has a standard plastic case which can be attached to the DIN rails with the width of 35 mm The unit drawing together with the overall and setting dimensions is provi...

Страница 9: ...ecture provides data routing between the Modbus RTU ASCII RS 485 network and Ethernet 10base T 100base T network The operating speed and availability of channels for direct access to the memory allows...

Страница 10: ...is provided with a globally unique MAC address during the production and can be connected to local networks with a protected access to Internet Figure 4 Structural diagram of the unit DC power Process...

Страница 11: ...tc in the air 4 1 5 Switching adjustment and maintenance of the unit should be conducted by the qualified personnel who is familiar with the provisions of this user manual 4 2 6 The following regulati...

Страница 12: ...d signal while contact B is used for the inverted signal 2 Switch the cable connection with Ethernet network supplied to the Ethernet socket and Ethernet network Any connection peculiarities depending...

Страница 13: ...connection to an Ethernet network using the HTTP protocol on port 80 PC connection can be established using the WEB browser When a client connects to port 80 the unit starts expecting requests for HTM...

Страница 14: ...provides a response to the client If the request is addressed to another unit the unit sends the request into the Modbus network and waits for a response from a unit on the network RS 485 indicator is...

Страница 15: ...l Collection Description Access Address Acting settings Current unit configuration In any mode read only 200 262 Saved settings The collection is saved regardless of power supply and further used as t...

Страница 16: ...String of characters 0 Configuration mode is available upon entering the valid password 100 119 Control command 0 3 writing in the configuration mode 0 0 no activity 1 Restart unit restart 2 Save save...

Страница 17: ...hole period of operation 140 Table 7 Unit configuration settings Parameter Min Max Factory setting Description Address Addressing in the Ethernet network Static IP address IP address 192 168 0 111 IP...

Страница 18: ...ernet network 515 520 Switching to Ethernet network Connection port for Modbus TCP 1 65535 502 Used in case of TCP connection to the unit via Ethernet to exchange data over Modbus TCP protocol 521 IP...

Страница 19: ...odbus TCP connection 0 1 0 0 Modbus TCP connection is maintained regardless of the connection hold time 1 if all connections to Modbus TCP are busy the new client requesting for a connection can be co...

Страница 20: ...the odd even check to verify odds 0 1 0 Used in case of data exchange between the units in Modbus network if odd even check is enabled The same value for all units in Modbus network 0 Parity check 1...

Страница 21: ...de Waiting for a response is terminated if the subsequent byte of the response has not been received within the given time as indicated for the reception of response Waiting time shall not be less the...

Страница 22: ...d is correct you shall be granted access to the setup mode Settings page appears with a list of parameters detailed in Table 7 If the password is incorrect the password request shall be displayed once...

Страница 23: ...see Table 5 before setting parameters Factory set password is 11111 i e write 49 ASCII code for one to record the factory set password to registers 0 4 If the password is correct the mode register se...

Страница 24: ...the expiry of the service life 9 2 Guaranteed storage life is 3 years 9 3 Warranty period is 36 moth from the date of sale The manufacturer shall provide a free repair of the unit within the warranty...

Страница 25: ...ipping box should be stored indoors at a temperature of 45 to 70C and relative humidity of no more than 80 with no vapors available in the air capable of producing harmful effect on the shipping box a...

Страница 26: ...D C 30 Patparganj Industrial Area 1st flr Delhi 110092 INDIA Tel 91 11 42143253 Tel Fax 91 11 43010600 Email info novatek electro in Web www novatek electro in _____________________________ __________...

Страница 27: ...Proper communication between units of a subnet is possible under several conditions 1 All units of a subnet have similar mask Most of small LANs are using 255 255 255 0 mask 2 Mask starts with a group...

Страница 28: ...irst three bytes of the IP address which are different from those specified in Table A 1 or the ET 485 factory IP address is already taken the configurable unit should be temporarily removed from the...

Страница 29: ...administrator 2 Click the icon of the connection with the right button and select Properties in the drop down menu The Properties window opens see Fig A 3 3 Select Internet Protocol TCP IP from the li...

Страница 30: ...30 ET 485 NOVATEK ELECTRO Figure 3 Connection properties window in Windows OS Figure 3 TCP IP properties window in Windows OS...

Страница 31: ...ection or acquire it from your ISP Connect the unit directly to the PC and change the parameters Enable manual MAC address and Manually set MAC address to have the manual MAC address enabled and value...

Страница 32: ...s shall be only available to a given client using a given protocol In case of no requests from the client over the long period the access returns to locked mode Note The setup mode is provided over an...

Страница 33: ...50 2 66 B 82 R 98 b 114 r 35 51 3 67 C 83 S 99 c 115 s 36 52 4 68 D 84 T 100 D 116 t 37 53 5 69 E 85 U 101 e 117 u 38 54 6 70 F 86 V 102 f 118 v 39 55 7 71 G 87 W 103 g 119 w 40 56 8 72 H 88 X 104 h...

Отзывы: