~ 17 ~
NOVATEK-ELECTRO
ET-485
Parameter
Description
Address
Modbus TCP loading, requests/sec
Number of requests processed in a second
136
Number of Ethernet network
congestions
Number of incoming buffer overflows for Ethernet (which may result
in a data loss) – since the start
137
Number of communication errors
Number of identified errors (connection/communication) after which
the work was continued, - since the start
138
Number of periodic restarts
Number of preset restarts – during the whole period of operation
139
Number of critical errors
Number of identified errors (failures) resulting in a restart of the unit -
during the whole period of operation
140
Table 7
– Unit configuration settings
Parameter
Min
– Max Factory setting
Description
Address
Addressing in the Ethernet network
Static IP-address
IP-
address
192.168.0.111 IP-address of the unit in Ethernet network shall be equal to this
value if dynamic addressing is disabled or not available.
500–503
Subnet mask
IP-mask 255.255.255.0 Used only together with a static IP-address
504-507
Gateway
IP-address 192.168.0.1
Used only together with a static IP-address, or as an IP-address
filter for DHCP-server
508-511
Enable dynamic
addressing via
DHCP-server
0-1
0
0: preset IP-address, mask and gateway is used for addressing
in Ethernet.
1: DHCP network server is used by the unit to determine IP-
address, mask and gateway. The parameters for static
addressing are used if server is unavailable
512