Read Status
4. Operation
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
71
Print Detector Data
An addresssable smoke detector’s ability to detect smoke can change over time as a result of component
deterioration due to environmental contaminants and dirt. Use the Print Detector Data function to print
the current sensitivity of each addressable smoke detector in the system.
To print each addressable smoke detector’s (sensitivity) data, press ‘3
’
then ENTER while viewing the
Print screen. A printout similar to the sample shown in Figure 24 will be generated to an optional printer
connected to the FACP.
Figure 24 Sample Detector Data Printout
Note:
If a printer is not available, it is possible to store Detector Data information by using the HyperTerminal feature
available on most personal computers running the Windows® operating system. Any settings which are configured in
this feature must reflect the printer settings detailed in "Printer Configuration" on page 39. Refer to the Windows®
Manual for information on the HyperTerminal feature.
The Chamber Reading
The Chamber Reading should be within the ranges indicated in Table 12. If the addressable smoke
detector’s Chamber Reading is not within the acceptable range, clean the detector, regenerate Detector
Data, and recheck the Chamber Reading. If the reading is still not within the acceptable range, replace
the detector immediately.
Model
Device Type
Acceptable Range
FSI-751
Low-Profile Intelligent Ionization Smoke Detector
270 - 1400
FSP-751
FSP-751T
Low-Profile Intelligent Photoelectric Smoke Detectors
500 - 1400
HPX-751
Analog Addressable Smoke Detectors
500 - 1400
FSD-751P
FSD-751RP
Intelligent Photoelectric Duct Detectors
500 - 1400
FST-751
FST-751R
Intelligent Thermal Detectors
600 - 1800
Table 12 Acceptable Ranges for Addressable Detectors
*******************************DETECTOR DATA********************************
DEVICE TYPE
DEVICE TYPE
DEVICE TYPE
DEVICE TYPE
CHAMBER READING
CHAMBER READING
CHAMBER READING
CHAMBER READING
TIME/DATE
TIME/DATE
TIME/DATE
TIME/DATE
SMOKE DET P01
947
03:52P Fri 09/28/01
SMOKE DET P02
908
03:52P Fri 09/28/01
SMOKE DET I03
968
03:52P Fri 09/28/01
SMOKE DET T04
1000
03:52P Fri 09/28/01