3. Programming
Program Change – Level One
50
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Password Change
While displaying the Program Menu, press the
4
key to change either of two passwords. One high level
password, defaulted to '00000', allows for point and system programming. A second lower level
password, defaulted to '11111', allows for status changes such as:
• Disable points/zones
• Clear history file
• Walktest enable
• Time and date set
• Program check
Pressing the
4
key will display the following:
Select the password to change by typing
*
or
#
, then enter the new password. As the new program or
status password is entered, it is displayed. When the enter key is pressed, the display reads “PRESS
ENTER IF OK, NNNNN=NEW PROGRAM PW”. After the
ENTER
key is pressed, the new password is
stored in EEPROM memory and the program returns to the program change screen. If BACKSPACE is
entered, the password remains unchanged and the program returns to the program change screen.
Load
Caution:
Changes to program entries occur as a result of the downloading process. After successful
downloading, make sure to perform the following steps:
1. Print out all programmed data via the print mode or manually view programmed entries and
compare to intended program data.
2. Test all affected control panel operations.
3. Immediately correct any problems that you find.
While displaying the Program Menu, program selection
5
sets up the control panel for transfer of its
application database from/to a Windows-based computer. This may be used to save the program that
exists in an control panel for security and future service reasons; or may be used to transfer a program
created off-line to the control panel. Refer to the Veri•Fire CD Medium System Programming Utility
help function for additional information. When the Load option is selected, the following screen will be
displayed:
The PC connects to the EIA-232 printer interface (instructions provided with the Veri•Fire CD Medium
System Programming Utility or see "Printer and PC Interface" on page 38). The left arrow key may be
used to return to the program change screen. Continue to press the left arrow key to return to the main
program screen.
At the completion of system programming, switch SW1 (Write Protect) should be set to the Write
Protect position to prevent inadvertent changes to programmed features. Slide the switch to the up
position to select the Write Protect feature.
*,NNNNN, E=LEVEL 1 PW
#,NNNNN, E=LEVEL 2 PW
!
CONNECT COMPUTER NOW
RUN PROGRAM FROM PC
Technical Manuals Online! - http://www.tech-man.com