4. Operation

Special System Timers

68

 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002

Waterflow Circuits Operation

If an alarm exists from a monitor module point that has a 

WATERFLOW

 type code, the Alarm Silence key 

will not function.

Disable/Enable Operation

Input points which are disabled do not cause an alarm or any CBE (Control-By-Event) activity. 
Disabled output points are held in the off state. All disabled points are treated as if they were in trouble, 
with the exception being the status label that displays is 

DISABL

.

Wiring Fault

If the SLC is wired and programmed for Style 6 and a single fault occurs, the control panel will detect 
the fault and drive both ends of the line, fully recovering from the fault.  The control panel latches the 
trouble and displays it until the 

SYSTEM

 

RESET

 key is pressed.  The display shows 

Style 6

 trouble type.

Technical Manuals Online! - http://www.tech-man.com

Содержание AFP-100

Страница 1: ...Intelligent Fire Panel AFP 100 AFP 100E Instruction Manual Document 51010 02 06 2002 Rev C1 PN 51010 C1 ECN 01 552 Technical Manuals Online http www tech man com...

Страница 2: ...fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do no...

Страница 3: ...g filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former and...

Страница 4: ...4 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 This page intentionally left blank Technical Manuals Online http www tech man com...

Страница 5: ...ntents AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 5 Table of Contents 1 Product Description 0 1 2 3 4 5 5 6 7 8 5 1 5 6 9 6 9 9 0 9 5 1 2 2 1 1 5 1 7 3 3 3 Technical Manuals Online http www t...

Страница 6: ...of Contents 6 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 3 5 1 2 Installation 9 0 9 1 0 1 2 32 4 1 5 0 5 4 8 3 3 0 5 5 5 9 9 9 3 Programming 4 6 7 2 Technical Manuals Online http www tech ma...

Страница 7: ...s AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 7 4 5 5 9 1 1 7 2 4 Operation 8 5 5 5 5 26 9 9 9 9 9 3 3 3 9 0 4 46 9 6 3 3 3 A 3 4 4 31 34 1 34 34 A 4 34 35 35 35 Technical Manuals Online http...

Страница 8: ...41 41 41 4 Appendix A Power Supply Calculations 4 Appendix B Electrical Specifications 6 0 43 43 43 43 6 43 44 1 5 44 Appendix C Software Zones 0 0 6 0 0 7 5 7 5 Appendix D NFPA Standard Specific Req...

Страница 9: ...device capacity 99 detectors and 99 monitor control modules 56 software zones Two main circuit board NACs Notification Appliance Circuits 300 mA resettable power 300 mA nonresettable power 3 0 amps N...

Страница 10: ...ng Manual 51253 Off line programming utility VeriFire CD Medium System Programming Utility PID 51249 Compatible Devices Notifier Device Compatibility Document 15378 Annunciators Annunciator Control Sy...

Страница 11: ...rails of the backbox Ample knockouts are provided for system wiring Transformer Assembly One XRM 24 XRM 24E for 220 240 VAC applications 100 VA transformer providing 3 6 amps maximum is provided stand...

Страница 12: ...ng conditions LCD Display The control panel uses a 40 character 2 lines x 20 characters high viewing angle LCD display with a character height of 3 16 inches The display includes a long life LED backl...

Страница 13: ...ACS COMM TB7 TERM COMM PC PRINTER TB3 Relays TROUBLE ALARM SUPV TB8 AC EARTH NEUTRAL HOT JP1 Battery Charger Disable Cut to disable FACP battery charger when using external charger J3 Battery Connecto...

Страница 14: ...VDC Nonresettable Power Output 300 mA 24 VDC Battery Charger up to 18 AH batteries Notification Appliance Circuits NACs Two NACs configurable for Style Y Class B or Style Z Class A are provided with v...

Страница 15: ...AH battery Both boxes are gray and provided with knockouts For 25 to 120 AH batteries use the CHG 120 Battery Charger When this charger is mounted in the BB 55 two 25 AH or one 55 AH battery may also...

Страница 16: ...System Programming Utility to program the control panel directly from most IBM compatible personal computers including laptops and portables equipped with a serial port Typically program files can al...

Страница 17: ...programming feature in the control panel FSI 751 Analog addressable low profile intelligent smoke detector that incorporates an ionization sensing chamber Designed to provide open area protection FSP...

Страница 18: ...two wire smoke detectors in addition to normally open contacts The FDM 1 provides two independent 2 wire IDCs at two separate consecutive addresses Wire supervised IDCs as NFPA Style B Class B or Styl...

Страница 19: ...is module is not addressable but listed here due to its use in an SLC Protects the system against wire to wire short circuits on the SLC It should be placed between groups of sensors in an SLC to isol...

Страница 20: ...side the FACP cabinet plugging into the J16 connector or may mount externally in a separate cabinet EIA 485 annunciator communications bus and filtered 24 VDC connections are required The UDACT transm...

Страница 21: ...ne Power LED Local sounder Silence Acknowledge switch and Remote functions Annunciator Expander Module AEM 16AT Expands the ACM 16AT by 16 system points and is identical in size and appearance Three e...

Страница 22: ...e acknowledge switch The Local Silence Acknowledge switch functions as local lamp test and silence for annunciator piezo The AFM 32A will not accept expander modules however multiple annunciators may...

Страница 23: ...For information and installation instructions refer to LCD 2X20 Remote Fire Annunciator manual Lamp Driver Annunciator Module LDM 32 Provides 32 alarm lamp driver outputs for connection to a custom g...

Страница 24: ...1 Product Description Annunciators 24 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 Notes Technical Manuals Online http www tech man com...

Страница 25: ...pendix A Power Supply Calculations on page 72 5 Connect AC DC power cables Power Connections on page 29 CAUTION Do NOT connect AC power and Do NOT connect batteries at this time 6 Connect DC power out...

Страница 26: ...les in the back surface of the backbox to provide secure mounting Mount the cabinet on a surface that is in a clean dry vibration free area The figure below shows the mounting hole location of the cab...

Страница 27: ...Installation AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 27 Shown below are dimensions for the AFP 100 cabinet Figure 5 AFP 100 Cabinet Dimensions TR 4 R Trim Ring Technical Manuals Online htt...

Страница 28: ...he Main Circuit Board over the backbox rails aligning mounting holes as shown below 6 Secure in place with four 4 screws Tighten securely 7 Plug transformer leads into circuit board connectors Top tra...

Страница 29: ...le 760 of the National Electrical Code NEC and or local codes Use 14 AWG 2 00 mm2 or larger wire with 600 VAC insulation rating In order for the AFP 100E to comply with Compatibility Directive 89 336...

Страница 30: ...edical attention Caution Do NOT connect the battery interconnect wire at this time Make this connection AFTER initial system primary powerup Observe polarity when connecting the battery Connect the ba...

Страница 31: ...cing is maintained between conductors of power limited and nonpower limited circuits or leave one unused terminal between power limited and nonpower limited circuits Note Note If relays are used as po...

Страница 32: ...and power limited Refer to the Device Compatibility Document for a listing of compatible notification appliances The two NACs Notification Appliance Circuits located on the main circuit board may be...

Страница 33: ...to 99 addressable detectors and an additional combination of up to 99 addressable pull stations control modules and monitor modules In addition the control panel supports two NACs Surge Suppression Su...

Страница 34: ...ower limited circuits 2 If this module is needed to drive power limited and nonpower limited relays that are next to each other make no connection to the Normally Open contact which separates the two...

Страница 35: ...align the J1 connector on the RTM 8F module board with the pins of J6 on the Main Circuit Board 5 Press firmly on the RTM 8F until it locks in place on the standoffs and the connector is seated onto...

Страница 36: ...e RTM 8F is not suitable for separate transmission of both alarm and trouble signals simultaneously to a remote station Output is power limited and wiring can leave the building C NC NO C NC NO C NC N...

Страница 37: ...LED from turning on when the Transmitter Output is not used no connections move jumper JP2 to the Local Energy Municipal Box position bottom two pins and install a dummy load across the Transmitter O...

Страница 38: ...el Programming For printer or PC programming instructions refer to System Edit on page 49 Installation Remote printers and PCs require 120 VAC 60 Hz or 240 VAC 50 Hz primary power Installation of a pr...

Страница 39: ...e following The Windows based VeriFire CD Medium System Programming Utility PIM 24 Interface Module 0 Figure 18 Printer and Computer Connections with PIM 24 BUFFER LARGE DATA BITS 7 PARITY EVEN STOP B...

Страница 40: ...2 Installation Printer and PC Interface 40 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 Notes Technical Manuals Online http www tech man com...

Страница 41: ...ity for off line programming When a programmed system is normal with no active alarms troubles or supervisories the SYSTEMS ALL NORMAL screen will be displayed as shown below To 1 program the system 2...

Страница 42: ...efer to Program Change Level One on page 44 Program Level 2 is where a qualified operator can access features such as Disable Clear History Walktest Time Change and Program Check For Program Level 2 t...

Страница 43: ...an be changed by the user and a method exists to clear one or both passwords If an invalid password is entered the display will read INCORRECT PASSWORD To exit from Programming operations at any time...

Страница 44: ...ontrol panel communicates with each individual addressable device and displays the type of device at each address location starting with detectors and then modules While autoprogramming the system the...

Страница 45: ...sor moves through the fields as you press the right arrow key triangle to the right of the ENTER key After moving into other fields you may return to a previous field by pressing the left arrow Change...

Страница 46: ...vice programmed and the cursor moves to the last character of the field Recall function The Recalled ADJ or NOUN field may now be changed letter by letter If the 0 key is pressed again with no other i...

Страница 47: ...lection is monitor as shown in the screen above Note that selection of a Type Code may change the functional operation of the addressable device as shown below Table 5 Monitor Module Type Codes Follow...

Страница 48: ...except during an alarm condition The following display will appear For example select detector address 3 program edit by pressing key detector followed by numeric key 3 followed by the ENTER key To s...

Страница 49: ...oral C California A U Annunciators with or without UDACT N one Z 56 Zones ZU 56 Zones Annunciator with UDACT2 P 198 Points PU 198 Points Annunciator with UDACT2 L P LCD 2X20 or Printer PC in use N one...

Страница 50: ...de or manually view programmed entries and compare to intended program data 2 Test all affected control panel operations 3 Immediately correct any problems that you find While displaying the Program M...

Страница 51: ...the screen similar to a Point Edit display but with the current status label ENABLE shown blinking The current status label may show NORMAL TROUBL DISABL ENABLE ALARM ACTIVE PROGRM TEST 01 ON OFF The...

Страница 52: ...key backspace which returns the control panel to the All Systems Normal display A one hour time out automatically returns the system to normal operation Shorted Alarm Condition When in Walktest the co...

Страница 53: ...row moves to the next digit The up and down arrows select A M or P M day of the week month day and year Pressing the ENTER key stores the time and date and returns to the Level 2 screen Check Program...

Страница 54: ...3 Programming Program Change Level Two 54 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 This page intentionally left blank Technical Manuals Online http www tech man com...

Страница 55: ...Program Corrupted SYSTEM TROUBLE UNPROGRAMMED SYSTEM Press 3 Press 2 Clear Historyt File ENTER to Clear Hist Backspace to Escape Change Time Date 00 00A TUE 00 00 00 Press 4 Time Date Program Check OK...

Страница 56: ...Press ENTER Press 1or 2 Press ENTER Example OFF BELL CKT B01 PANEL CIRCUIT Z Press 1 ENTER Press 2 ENTER EVENT HISTORY START EVENTS IN HIST XXXX Program Status Print History Print Display Point AA His...

Страница 57: ...Screen Options Flowchart 3 Programming AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 57 Notes Technical Manuals Online http www tech man com...

Страница 58: ...STEP key In addition if an alarm exists it turns off all silenceable circuits and causes the Alarm Silence LED to turn on It also sends an Alarm Silenced message to the printer the history file and t...

Страница 59: ...more supervisory conditions occur such as a sprinkler valve tamper condition It illuminates steady when you press the ACKNOWLEDGE STEP key or the ALARM SILENCE key The SUPERVISORY LED turns off when...

Страница 60: ...on page 53 The control panel performs the following functions at regular intervals while in normal mode Polls all devices on the SLC checking for valid reply alarms troubles etc Monitors the AC input...

Страница 61: ...icates smoke detector Point type and address in this example P01 indicates Photoelectric detector assigned to address 01 The information displayed in the second line in the example above provides the...

Страница 62: ...wing information ADJ user programmed adjective descriptor from library list or custom entry five characters maximum NOUN user programmed noun descriptor from library list or custom entry ten character...

Страница 63: ...e Systems All Normal message is shown on the LCD display and stored in the history and printer files Trouble restore occurs even if the troubles were never acknowledged auto restore If the ALARM SILEN...

Страница 64: ...e Supervisory LED not Alarm flashes The Display Status label is Active Supervisory relay is activated Silenced alarms are not resounded Timers are not started The alarm relay is not activated A typica...

Страница 65: ...0 of its alarm threshold for a 24 hour period a Maintenance Alert message will be automatically displayed signaling that the detector needs servicing Automatic Test Operation An automatic test of each...

Страница 66: ...rcuits are not activated for 15 seconds During this time if the ACKNOWLEDGE STEP key is pressed the panel sounder is silenced and the notification appliances will not activate for up to three minutes...

Страница 67: ...addressable smoke detector s alarm is ignored for a Retard period of 13 seconds and the detector s alarm condition is automatically reset There will be no alarm indication at the control panel during...

Страница 68: ...vity Disabled output points are held in the off state All disabled points are treated as if they were in trouble with the exception being the status label that displays is DISABL Wiring Fault If the S...

Страница 69: ...timer Pressing the left arrow backspace key deletes the previous entry If there is no previous entry it will cancel the Read Status operation and return to the previous display To cancel Read Status...

Страница 70: ...a Not Installed message on the display Read History The control panel provides a history file that can store up to 500 events such as Point Status System Troubles and Acknowledge Step Alarm Silence D...

Страница 71: ...Windows Manual for information on the HyperTerminal feature The Chamber Reading The Chamber Reading should be within the ranges indicated in Table 12 If the addressable smoke detector s Chamber Readin...

Страница 72: ...un continuously without any disconnect devices from the power source to the fire alarm control panel Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Cod...

Страница 73: ...1 X 0 08 0 08 RTM 8F one max X 0 009 ACM 8R X 0 0302 2 TB4 nonresettable terminals auxiliary power 300 mA filtered 24 VDC 5 120Hz ripple 10 mVRMS AFM 16AT or AFM 32A one max X 0 042 AEM 16AT or AEM 3...

Страница 74: ...mps Main Circuit Board 1 X 0 168 0 168 RTM 8F one max X 0 1462 2 All RTM 8F Relays activated ACM 8R X 0 1583 3 All eight ACM 8R Relays activated on a single module AFM 16AT AFM 32A one max X 0 0564 4...

Страница 75: ...uire the Notifier BB 17 battery box The AFP 100 main circuit board allows disabling of AFP 100 battery charger if using the CHG 120 Battery Charger for 25 AH to 100 AH batteries requires separate hous...

Страница 76: ...de nonregulated special purpose power limited circuitry with the following Alarm Trouble and Supervisory Relays Specifications for the relays available from TB3 are Maximum Charging Circuit Normal Fla...

Страница 77: ...S 24D instead of more electronically noisy notification appliances such as electromechanical bells or horns Four wire smoke detector 24 VDC nominal Maximum ripple voltage 10 mVRMS Maximum standby curr...

Страница 78: ...50 15 18 AWG 0 75 mm2 minimum FMM 1 and FMM 101 power limited Initiating Device Circuit Maximum loop wire resistance is 40 ohms for the FMM 1 and 20 ohms for the FMM 101 2 500 760 12 18 AWG 3 25 0 75...

Страница 79: ...Wire Requirements Appendix B Electrical Specifications AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 79 Notes Technical Manuals Online http www tech man com...

Страница 80: ...are zones Use the charts on the following pages to help in zoning the system Note that monitor and control modules make up one group of 99 addresses It is critical that addresses of detectors are not...

Страница 81: ...es for inputs and outputs Figure 25 Software Zoning Examples INPUT DEVICES OUTPUT DEVICES SOFTWARE ZONES PHOTO 02 PHOTO 01 MONITOR 01 ZONE 01 CONTROL 03 CONTROL 04 CONTROL 05 CONTROL 06 CONTROL 07 ZON...

Страница 82: ...ce Type Zone Number ADJ 5 char max NOUN 9 char max 01 FSP 751 1 FIRST HALL 51 02 FSP 751 1 ELEV LOBBY 52 03 FSI 751 2 2ND FLOOR 53 04 FSI 751 2 ROOM 210 54 05 FSP 751 2 3 3RD FLOOR 55 06 FSP 751 3 MEZ...

Страница 83: ...umber ADJ 5 char max NOUN 9 char max Address Device Type Zone Number ADJ 5 char max NOUN 9 char max 01 FMM 1 1 WEST HALL 51 02 FMM 101 2 EAST STAIRWELL 52 03 FCM 1 1 EAST HALL 53 04 FCM 1 1 1ST FLOOR...

Страница 84: ...ppendix C Software Zones Sample Programming Sheets 84 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 Zoning Sheet ZONES OUTPUT DEVICES INPUT DEVICES Technical Manuals Online http www tech man com...

Страница 85: ...s Device Type Zone Number ADJ 5 char max NOUN 9 char max 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74...

Страница 86: ...Address Device Type Zone Number ADJ 5 char max NOUN 9 char max 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 7...

Страница 87: ...Sample Programming Sheets Appendix C Software Zones AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 87 Notes Technical Manuals Online http www tech man com...

Страница 88: ...ises Unit and Remote Station Service Protected Premises Unit requires connection to a compatible listed Central Station DACR or Protected Premises Receiving Unit by one of the following MS 5012 Contro...

Страница 89: ...ight of the AFP 100 main circuit board must be positioned in the down position for this application This prevents the transmission of a trouble on the loss of AC power Figure 26 Central Station Servic...

Страница 90: ...2 06 2002 The following figure illustrates the internal mounting of a UDACT Figure 27 Internal installation of UDACT J10 TROUBLE PC PRINTER TERM COMM RS 232 PC PRINTER RS 485 TERM MODE TROUBLE A B B A...

Страница 91: ...ipal Box is 3 ohms 2 Cut JP4 on the AFP 100 main circuit board to supervise placement of RTM 8F module and circuit 3 Jumper JP2 must be in position LE MUNCPL BOX for use in this application 4 For info...

Страница 92: ...alarm and trouble transmission or ALARM ONLY for alarm transmission only 4 For information on UL Power limited wiring requirements see UL Power limited Wiring Requirements on page 34 Figure 29 NFPA 72...

Страница 93: ...r 2 This AFP 100 Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System Figure 30 Proprietary Protective Signaling System Form A relay contact programmed to activa...

Страница 94: ...Appendix D NFPA Standard Specific Requirements Proprietary Protective Signaling Systems 94 AFP 100 AFP 100E Instruction PN 51010 C1 02 06 2002 Notes Technical Manuals Online http www tech man com...

Страница 95: ...ible indication 21 automatic test 65 Autoprogram Feature 41 45 Autoprogramming mode 44 Auto silence Timer 67 available words list of 45 B backbox 11 29 backlight LED 12 backspace key 12 Bases detector...

Страница 96: ...dule 19 Form C relays 20 22 Four wire smoke detector power 77 FRM 1 19 Function keys 12 functions of control panel normal 60 FZM 1 18 52 G general alarm zone 65 graphic annunciator 23 ground connectio...

Страница 97: ...rsal Output 36 polls 44 power output connections 31 Power Supply remote 15 power up 42 power emergency standby 15 power limited requirements relays 31 wiring 34 primary power 29 Print Program 70 print...

Страница 98: ...tem Status LED Indicators 59 System Trouble 14 System Trouble LED 44 59 61 T TB3 Relay connections 31 TB4 DC power connection 31 TB5 ACS Mode connection 21 22 32 TB7 Terminal Mode connection 32 teleph...

Страница 99: ...to NOTIFIER 12 Clintonville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products...

Страница 100: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is an operation of Technical Manuals Online http www tech man com...

Отзывы: