Addressable Devices
1. Product Description
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
19
Control Module, NAC - FCM-1
Addressable Control Module used as Notification Appliance Circuits
(NACs) to power and supervise compatible, UL-listed notification
appliances. Wired supervised NACs as NFPA Style Y (Class B) or
Style Z (Class A). The modules come with a thermoplastic cover for
mounting to a 4-inch square mounting box.
Control Module, Relay - FRM-1
Similar to the FCM-1 except used as a Form-C control relay module.
Fault Isolator Module - IXO-X
This module is not addressable, but listed here due to its use in an
SLC. Protects the system against wire-to-wire short circuits on the
SLC. It should be placed between groups of sensors in an SLC to
isolate short circuit problems and protect the rest of the loop so it can
continue to operate normally.
Pull Station - NBG-12LX
A non-coded addressable manual pull station with key-lock reset
feature. An FSM-101addressable module is housed within the pull
station.