Program Change – Level One
3. Programming
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
49
System Edit
The System Edit function is selected by pressing the
3
key. The system edit screen appears as shown
below.
Use the up and down arrow keys to scroll through the choices for each option and the left and right
arrow keys to move from option to option.
There are nine system function options. The factory default selections and user option selections are
shown below:
Table 7 System Function Options
Function
Default
Option Selection
V = Alarm
Verification
(N)one
(Y) 120 seconds
I = Silence Inhibit
(N)one
(Y) 60 seconds
1
A = Autosilence
(N)one
(Y) 10 minutes
1
P = Presignal
(N)one
(Y) 3 minutes with 15 second Acknowledge
1
C = Bell Code
(N)one
(M) = March Time
(T) = Temporal
(C) = California
A/U = Annunciators
with or without
UDACT
(N)one
(Z) = 56 Zones
(ZU) = 56 Zones Annunciator with UDACT
2
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT
2
L/P = LCD-2X20 or
Printer/PC in use
(N)one
L = LCD-2X20 Series installed
P = Printer or local PC installed
S = SLC style
(4) = Style 4
(6) = Style 6
R = Alarm/Trbl
Reminder
(N)o
(Y)es = Sound onboard piezo every 15 seconds
during alarm and every two minutes during
trouble after pressing the
ACKNOWLEDGE
or
SILENCE
key.
1 Requires prior approval of Local Authority Having Jurisdiction.
2 When the UDACT has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD
display and printer hardcopy. The history file will also be updated with this information. For zone
annunciation, up to 56 zones, use AFM Series Annunciators or LDM Series Annunciators. For 198
point annunciation, use the LDM Series Annunciators.
V=N I=N A=N P=N C=N
A/U=N L/P=N S=4 R=N
Technical Manuals Online! - http://www.tech-man.com