Enter Programming Mode
3. Programming
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
43
Enter Programming Mode
From the “SYSTEMS ALL NORMAL” screen, press the
ENTER
key. The screen below will appear:
To enter the programming mode, press
1
. The display will read as follows:
Passwords
There are two factory set programming passwords, '00000' and '11111', which will access two different
screens as indicated below. From either of the screens, access to specific system and device
programming may be obtained. All programming entries are stored in nonvolatile memory. The factory
set passwords can be changed by the user and a method exists to clear one or both passwords. If an
invalid password is entered, the display will read 'INCORRECT PASSWORD'. To exit from
Programming operations at any time, press the Backspace (left arrow) key repeatedly.
Note:
For Canadian applications, both passwords must be changed from the factory settings.
Entering the Level 1 password (default =
00000
) will cause the following screen to appear (refer to
"Program Change – Level One" on page 44):
Entering the Level 2 password (default =
11111
) will cause the following screen to appear (refer to
"Program Change – Level Two" on page 51):
1=PROGRAMMING
2=RD>STATUS 3=AC/BAT
KEY PASSWORD, ENTER
0=CLR 1=AUTO 2=POINT
3=SYS 4=PWORD 5=LOAD
1=DISABL 2=CLR HIST
3=WALK 4=TIME 5=CHEK
Technical Manuals Online! - http://www.tech-man.com