Appendix D: NFPA Standard-Specific Requirements
Overview
88
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Appendix D: NFPA Standard-Specific Requirements
Overview
The AFP-100 is designed for use in commercial, industrial and institutional applications and meets the
requirements for service under the National Fire Protection Association (NFPA) Standards outlined in
this Appendix.
Minimum Requirements
The minimum system components required for compliance with the appropriate NFPA standard are
listed below:
•
AFP-100 Control Panel
- Contains the main control board, cabinet (backbox and door), main
power supply transformer and power supply.
•
Batteries
- Refer to "Appendix A: Power Supply Calculations" on page 72, for Standby Power
Requirements.
•
Initiating Devices
- Connected to one of the control panel's Initiating Device Circuits.
•
Notification Appliances -
Connected to the control panel's Notification Appliance Circuit via a
control module.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA 72 National Fire Alarm
Standards as listed below:
Central and Remote Station Service
Central Station Service (Protected Premises Unit) and Remote Station Service (Protected Premises
Unit) requires connection to a compatible listed Central Station DACR or Protected Premises Receiving
Unit by one of the following:
•
MS-5012 Control Communicator -
This unit must be installed as outlined in "Central &
Remote Station Service (Protected Premises Unit)" on page 89. For additional information see
the
MS-5012 Control Communicator Manual
.
•
UDACT -
This unit is to be installed in accordance with the
UDACT Instruction Manual
. See
Figure 27 on page 90 for an illustration of an internal installation of the UDACT.
Auxiliary Fire Alarm System
For connection to a compatible listed Local Energy Municipal Box the following unit is required:
•
RTM-8F Relay/Transmitter Module -
This unit must be connected as outlined in "Auxiliary
Fire Alarm System" on page 91. For additional information see "Installing a RTM-8F Module"
on page 35.
Remote Station Fire Alarm System
RTM-8F Relay/Transmitter Module for connection to the Notifier RS82 Remote Station Receiver. See
"Remote Station Protective Signaling System" on page 92, for installation instructions for this unit.
Proprietary Fire Alarm System
AFP-100 Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See "Proprietary
Protective Signaling Systems" on page 93, for installation instructions for this unit.