Installation |
18
* Dimensions and brackets are recommendations based on best practice. OEM must verify operation if they are not followed.
Figure 15: Steam Distributor Below Humidifier With Obstruction (Hose)
Figure 16: Common Steam Line Errors
Steam line
not sloped
No condensate
trap at vertical
transition
No drop to
condensate
trap
1ft (30 cm)
min. before
any bend*
12 in.
(30 cm)
min. radius*
Obstruction
Use full size condensate tee
at low point. Slope lines up
to “T” and immediately after it.
Hose will soften
over time
proper support
Is necessary
Support brackets*
1 ft (30 cm) min.
(recommended)
To drain
To drain
2 in.
(5 cm)
min.
1 ft (30 cm)