| Installation
Figure 13: Condensate Traps
* Dimensions and brackets are recommendations based on best practice. OEM must verify operation if they are not followed.
Figure 14: Steam Distributor Above Humidifier (Hose)
12 in. (30 cm)
min drop to
top of ‘P’ Trap
P Trap min
6 in. (15 cm)
or
duct static
pr 2 in
whichever is
greater
Tee is same size
as steam line
Use a full size tee, not a 90
degree elbow for vertical
to horizontal transitions.
‘P’ Traps Use:
- NORTEC 0.375 in condensate hose
- 1/4 in Med-L copper tubing, or
- 0.375 in stainless steel tubing
Condensate drains must be sloped down.
Route to humidifier fill cup if possible.
1 ft (30 cm)
before any
bend*
12 in.(30 cm)
min. radius*
Condensate
trap
Condensate
line
Connect steam
hose to cylinder
Connect condensate
hose to fill cup
or to drain.
2 in. (5 cm)
min.
1 ft (30 cm)
Support
brackets*