47
Installation
Nortec GS
2583703_EN_1608
5.8.2
Exhaust Vent Installation (CS/NX Model)
The Nortec GS (CS/NX model) humidifier must be installed as a Category IV fan-assisted gas appliance.
In addition to the specific requirements described in
"Installation as a Category IV Appliance" on page 48
, refer
to the general requirements –
"General Requirements" on page 43
.
All vent installations must be in accordance with national and the local regulations.
The exhaust outlet on the unit has a female connection (metric). Each unit is supplied with a metric to
imperial adaptor (with internal gaskets) to accomodate imperial vent sizes.
To connect the exhaust vent, first insert the adaptor into the exhaust outlet and secure it to the top panel
with four sheetmetal screws (supplied) – refer to
Figure 22
. Then slide the exhaust vent into the adaptor
until it bottoms out, and secure it with the clamp built into the adaptor. A sealant is not required.
Make sure that the exhaust vent is supported by hangers or pipe straps so that there is no load on the
humidifier.
Figure 22:
1
2
3
4
Nortec GS Exhaust Vent Connection (CS/NX Model Only)
1 Vent, exhaust – CPVC or type BH (CPVC only for GS 50-CS/NX)
2 Adaptor, exhaust – plastic (supplied)
3 Screw, sheetmetal (
×
4, supplied)
4
Outlet, humidifier exhaust
Содержание GS
Страница 3: ...INSTALLATION MANUAL Gas fired Steam Humidifier Nortec GS 2583703_EN_1608 ...
Страница 12: ...6 For Your Safety 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 14: ...8 Receiving and Storage 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 20: ...14 Product Overview 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 72: ...66 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 78: ...72 Product Specifications 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 82: ...iv Appendix A 2583703_EN_1608 Nortec GS This page intentionally left blank ...