30
Installation
2583703_EN_1608
Nortec GS
5.5.2
Best Practices for Installing Steam and Condensate Lines
Nortec recommends that you observe the following best practices for installing atmospheric steam lines
and condensate lines.
Steam Line
– Use rigid steam pipe made of copper (MED Type-L) or stainless steel (minimum DIN 1.4301) ex
-
clusively. Steam pipes made of any other materials may adversely affect the operation of the unit,
and will void the warranty.
–
Refer to
Table 12
for the required minimum internal diameter of the steam pipe. The internal diameter
of the steam pipe can be expanded, but once expanded a reduction in diameter is not permitted,
except at the steam distributor.
Table 12:
Steam Pipe Diameter
Model
Minimum Internal Diameter
Maximum Equivalent
Steam Line Length
GS 50
1.75 in (45 mm)
45 ft (14 m)
GS 100
1.75 in (45 mm)
69 ft (21 m)
GS 150
3 in (76 mm)
100 ft (30 m)
GS 200
3 in (76 mm)
120 ft (37 m)
GS 300
3 in (76 mm)
150 ft (46 m)
GS 450
4 in (102 mm)
180 ft (55 m)
GS 600
4 in (102 mm)
260 ft (79 m)
– The length of the steam line should be kept as short as possible. It should not exceed the maximum
equivalent length shown in
Table 12
. Exceeding the maximum length can affect performance of the
unit, and may void the warranty. Backpressure in the line combined with duct static pressure must
not exceed 6 in H2O (1.49 kPa) for compact units, and 10 in H2O (2.49 kPa) for full-size units. Refer
also to
Table 13 on page 31
for equivalent length of typical steam line fittings.
IMPORTANT!
When calculating the backpressure on the unit, include allowance of approxi
-
mately 0.12 in H2O for every foot (100 Pa for every meter) of steam line, and every 90° elbow.
– Use long radius elbows for steam pipes. This minimizes backpressure and formation of condensation.
IMPORTANT!
When determining the length and routing of steam lines, allowances must also
be made for thermal expansion.
– The steam line from the humidifier must lead straight upwards for a minimum of 12 in (300 mm),
before continuing on to the steam distribution system – refer to
Figure 12 on page 29
. The steam line
must have a minimum upslope of 10°, or a minimum downslope of 2° – refer to
Figure 13 on page 31
.
– Use only Nortec steam hose between the steam outlet on the humidifier and the steam distributor.
Other types of steam hoses can affect performance of the unit, and may void the warranty. The
length of the steam hose must be kept to a minimum. The minimum bend radius of the steam hose
is 300 mm. The steam hose must not sag, and must have a minimum upslope of 10°, or a minimum
downslope of 2° to the steam distributor.
IMPORTANT!
When calculating the backpressure on the unit, include allowance of approxi
-
mately 0.12 in H2O for every foot (100 Pa for every meter) of steam hose.
Allowances must also be made for shrinkage in the length of the steam hose due to aging.
– Use short lengths of steam hose to connect the steam line to the humidifier or steam distributor.
Secure the steam hoses with gear clamps.
Содержание GS
Страница 3: ...INSTALLATION MANUAL Gas fired Steam Humidifier Nortec GS 2583703_EN_1608 ...
Страница 12: ...6 For Your Safety 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 14: ...8 Receiving and Storage 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 20: ...14 Product Overview 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 72: ...66 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 78: ...72 Product Specifications 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 82: ...iv Appendix A 2583703_EN_1608 Nortec GS This page intentionally left blank ...