Product Overview
Nortec GS
2583703_EN_1608
4.3.1
High Altitude De-rating
All high altitude installations have a de-rating of the input capacity. All Canadian models have an auto
-
matic 10% de-rating for installations between altitudes of 2000-4500 ft (610-1372 m). For U.S. models,
refer to
Table 3
for the applicable de-ratings.
Table 3:
High Altitude De-rating
Altitude
De-rating (%)
Feet (ft)
Meters (m)
0-2000
0-610
0
2001-3000
610-915
8
3001-4000
915-1220
12
4001-4500
1220-1370
16
4501 and higher
1370 and higher
Contact factory
4.4
Options
Table 4
shows the options for the Nortec GS humidifier. Contact your Nortec representative for details.
Table 4:
Nortec GS Series Options
Option
Application
Mounting stand
Stand for independent mounting of the Nortec GS humidifier on the floor.
Natural gas or propane
Factory-installed gas valve for using either natural gas or propane in the Nortec GS humidi
-
fier.
4.5
Accessories
Table 5
shows the accessories for the Nortec GS humidifier. Contact your Nortec representative for details.
Table 5:
Accessories for the Nortec GS Series
Accessory
Application
Steam distributor – ASD,
BSD, CSD
Steam distribution system for use in an air duct.
SAM-e steam distribution
manifold, and mini SAM-e
Steam distribution system for use in an air duct where reduced absorption distance is re
-
quired.
Blower pack (remote-
mounted)
For direct room humidification or use in conditioned spaces without a built-in air distribution
system. The Nortec GS 50/100 model can use a remote-mounted blower pack for steam
distribution (blower pack ordered as an accessory).
Digital or analog control
humidistat with either On/Off
or modulating operation
Input device used to meter the output of the humidifier based on the sensed relative humidity.
The humidistat can be installed in the conditioned space that is being humidified, or within
the duct.
Digital RH transducer
Input device used to communicate the relative humidity in a conditioned space or a duct to
the humidifier.
Digital or analog high limit
humidistat with either On/Off
or modulating operation
Input device used to limit the output of the humidifier by either shutting it down or throttling it
down when the humidity in the duct approaches the high limit.
Air proving switch
Input device to ensure that humidification only occurs when air is moving through the duct.
Outdoor temperature sensor
Input device used to communicate the outdoor temperature to the humidistat so that it can
lower the setpoint value during cold weather to prevent condensation on exterior windows/
surfaces.
Содержание GS
Страница 3: ...INSTALLATION MANUAL Gas fired Steam Humidifier Nortec GS 2583703_EN_1608 ...
Страница 12: ...6 For Your Safety 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 14: ...8 Receiving and Storage 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 20: ...14 Product Overview 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 72: ...66 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 78: ...72 Product Specifications 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 82: ...iv Appendix A 2583703_EN_1608 Nortec GS This page intentionally left blank ...