5.10 Humidity Control Systems
5.10.1
Control Device Locations
The following schematic describes a potential system setup with respect to control devices. Refer to
Figure 24
,
Figure 24:
φ
φ
max
φ
Δp
1
1
2
3
System Setup Schematic
1 Humidistat or humidity sensor
2 High limit humidistat or humidity sensor
3 Switch, air proving
Notes:
•
Locate the air proving switch in the same duct as the humidifier’s distributor so that it can sense air
flow (or lack thereof).
•
Locate the high limit humidistat downstream of the humidifier’s distributor so that it can sense a
duct that is over-humidified. Recommended setting is 85% RH. Locate it downstream of the distribu
-
tor – at least 5x the absorption distance away. If the absorption distance is not known, locate it at
least 10 feet (3 m) downstream from the distributor. Can be a humidistat (modulating or On/Off), or
a humidity sensor.
•
Humidity sensors and humidistats can be modulating or On/Off. Preferred location is in the return
duct, as the supply air is well mixed with the room air at this location. Avoid placing near discharge
diffuser, near doorways, in sunlight, or in airflow “dead-zones”.
Содержание GS
Страница 3: ...INSTALLATION MANUAL Gas fired Steam Humidifier Nortec GS 2583703_EN_1608 ...
Страница 12: ...6 For Your Safety 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 14: ...8 Receiving and Storage 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 20: ...14 Product Overview 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 72: ...66 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 78: ...72 Product Specifications 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 82: ...iv Appendix A 2583703_EN_1608 Nortec GS This page intentionally left blank ...