20
Installation
2583703_EN_1608
Nortec GS
Power Supply
The power supply to the humidifier must not exceed the rated current draw indicated on the speci
-
fication label. Refer to
Figure 3 on page 10
.
The power supply must have an external dedicated fused disconnect switch located in the immediate
vicinity of the humidifier. The fusing must not exceed the maximum current draw of 15 A.
5.4
Mounting the Humidifier
Before mounting the Nortec GS humidifier, refer to
"Site Requirements" on page 18
for the location and
mounting requirements.
5.4.1 Clearances
The required clearances are listed in
Table 9 on page 21
, and the suggested clearances are listed in
Table 10 on page 21
. Refer to
Figure 7
. Consult local and national installation regulations. Nortec does not
accept responsibility for violations of the installation codes.