Nortec GS
Water Connections
Water quality meet the requirements listed in
Table 6 on page 18
?
Shutoff valve and union fitting installed in supply line?
Water supply piping to humidifier minimum 1/2 in (13 mm) diameter? Plastic or stainless steel pipe,
if using demineralized water?
5 μm water filter (optional, but recommended) installed in the supply line close to the humidifier?
Water supply temperature 34-77 °F (1-25 °C)?
Water supply surge-protected and pressure regulated to 30-80 psig (207-550 kPa)?
Check for leaks in the water supply line?
Air gap funnel in the floor located away from the control cabinet in the humidifier?
Air gap funnel minimum 2-1/2 in (64 mm) in diameter?
Drain pipe between air gap funnel and building drain have a minimum internal diameter of 1-1/2 in
(38 mm)? Copper or stainless steel pipe?
Drain hose from humidifier empty into the air gap funnel without touching its sides or bottom? Drain
hose have a minimum constant downslope of 1.2°, and secured with hose clamp? Drain hose rated
for 212 °F (100 °C)?
Water supply line and drain lines flushed? Strainer in the fill valve free of debris?
Condensate hose installed (CS/NX models only)? Hose rated for 212 °F (100 °C)?
Condensate trap inside unit primed with water?
Combustion Air Connection – Space Air Installation
Fresh combustion air requirements for the room/space (
Table 14 on page 40
and all national and local
regulations) satisfied?
Elbow installed at the intake air inlet (on Nortec GS 150-600 units)?
Combustion Air Connection – Sealed Combustion Installation
All relevant national and local regulations for sealed combustion installation satisfied?
Intake vent length does not exceed an equivalent length of 100 ft (30 m)? If unit is a Nortec GS 50
using propane gas, is it limited to 50 ft (15 m)? Maximum six bends?
Vent diameter as listed in
Table 15 on page 41
, and uniform over the entire run?
All joints and seams sealed with appropriate sealant?
Intake vent supported?
Spacing between air intake terminal and exhaust vent terminal minimum 3 ft (1 m)?
Intake vent heated and insulated in cold climates?
Exhaust Vent Connection
Exhaust vent installed to meet all national and local codes, vent manufacturer and Nortec require
-
ments?
Proper clearances maintained between exhaust vent and combustible materials?
Exhaust vent diameter as listed in
Table 16 on page 44
, and uniform over the entire run?
Exhaust vent length does not exceed an equivalent length of 100 ft (30 m)? If unit is a Nortec GS 50
using propane gas, is it limited to 50 ft (15 m)? Maximum six elbows in the exhaust vent?
Exhaust vent diameter uniform over the entire run?
E
xhaust vent secured properly with hangers or pipe straps?
Содержание GS
Страница 3: ...INSTALLATION MANUAL Gas fired Steam Humidifier Nortec GS 2583703_EN_1608 ...
Страница 12: ...6 For Your Safety 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 14: ...8 Receiving and Storage 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 20: ...14 Product Overview 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 72: ...66 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 78: ...72 Product Specifications 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Страница 82: ...iv Appendix A 2583703_EN_1608 Nortec GS This page intentionally left blank ...