4.3 PARAMETER LIST AND BREAKDOWN TABLE
(1) Electronic control fault table
Can be judged according to the remote controller failure code and troubleshooting
FREQUENCY CONVERSION BOARD FAULT TABLE:
Protect/fault
Fault
display
Reason
Elimination methods
Standby
Non
Normal boot
Non
Inlet Temp.
Sensor Fault
P01
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Outlet Temp.
Sensor Fault
P02
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Ambient Temp.
Sensor Fault
P04
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Coil Temp.
Sensor Fault
P05
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Suction Temp.
Sensor Fault
P07
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Discharge Temp.
Sensor Fault
P081
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
High Pressure
Prot.
E01
The high-pressure switch is broken
Check the pressure switch and cold
circuit
Low Pressure
Prot.
E02
Low pressure1 protection
Check the pressure switch and cold
circuit
Flow Switch
Prot.
E03
No water/little water in water
system
Check the pipe water flow and
water pump
Anti-freezing
Prot.
E07
Water flow is not enough
Check the pipe water flow and whether
water system is jammed or not
Primary Anti-freezing
Prot.
E19
The ambient temp. Is low
Secondary Anti-
freezing Prot.
E29
The ambient temp. Is low
Inlet and outlet
temp. too big
E06
Water flow is not enough
and low differential pressure
Check the pipe water flow and whether
water system is jammed or not
Low temperature
protection
Non
The environment temp. is low
Comp.
Overcurrent Prot.
E051
The compressor is overload
Check whether the system of the
compressor running normally
Exhaust Air over
Temp Prot.
P082
The compressor is overload
Check whether the system of the
compressor running normally
Communication
Fault
E08
Communication failure between
wire controller and mainboard
Check the wire connection between
remote wire controller and main board
Antifreeze Temp.
Sensor Fault
P09
antifreeze temp sensor is broken or
short circuited
check and replace this temp sensor
Waterway
Anti-freezing Prot.
E05
water temp. or ambient temp. is
too low
EC fan feedback
Fault
F051
There is something wrong with fan
motor and fan motor stops running
Check whether fan motor is broken
or locked or not
Pressure sensor
Fault
PP
The pressure Sensor is broken
Check or change the pressure
Sensor or pressure
Fan Motor1
Fault
F031
1. Motor is in locked-rotor state 2.The wire
connection between DC-fan motor
module and fan motor is in bad contact
1. Change a new fan motor
2. Check the wire connection and make
sure they are in good contact
Fan Motor2
Fault
F032
1. Motor is in locked-rotor state 2.The wire
connection between DC-fan motor
module and fan motor is in bad contact
1. Change a new fan motor
2. Check the wire connection and make
sure they are in good contact
Communication Fault
(speed
control module)
E081
Speed control module and main board
communication fail
Check the communication connection
Protection/fault
Fault
display
Reason
Elimination methods
Drv1 MOP alarm
F01
MOP drive alarm
Recovery after the 150s
Inverter offline
F02
Frequency conversion board and main
board communication failure
Check the communication connection
IPM protection
F03
IPM modular protection
Recovery after the 150s
Comp. Driver Failure
F04
Lack of phase, step or drive hardware
damage
Check the measuring voltage Check
frequency conversion board hardware
DC Fan Fault
F05
Motor current feedback open circuit or
short circuit
Check whether current return wires
connected motor
IPM Overcurrent
F06
IPM Input current is large
Check and adjust the current measurement
Inv. DC Overvoltage
F07
DC bus voltage>Dc bus over-voltage
protection value
Check the input voltage measurement
Inv. DC Less voltage
F08
DC bus voltage<Dc bus over-voltage
protection value
Check the input voltage measurement
Inv. Input Less voltage F09
The input voltage is low, causing the input
current is high
Check the input voltage measurement
Inv. Input Overvolt.
F10
The input voltage is too high, more than
outage protection current RMS
Check the input voltage measurement
Inv. Sampling Volt.
F11
The input voltage sampling fault
Check and adjust the current measurement
Comm. Err DSP-PFC
F12
DSP and PFC connect fault
Check the communication connection
Input Over Cur.
F26
The equipment load is too large
PFC fault
F27
The PFC circuit protection
Check the PFC switch tube short circuit or not
IPM Over heating
F15
The IPM module is overheat
Check and adjust the current measurement
Weak Magnetic Warn F16
Compressor magnetic force is
not enough
Inv. Input Out Phase
F17
The input voltage lost phase
Check and measure the voltage adjustment
IPM Sampling Cur.
F18
IPM sampling electricity is fault
Check and adjust the current measurement
Inv. Temp. Probe Fail
F19
Sensor is short circuit or open circuit
Inspect and replace the sensor
Inverter Overheating
F20
The transducer is overheat
Check and adjust the current measurement
Inv. Overheating Warn F22
Transducer temperature is too high
Check and adjust the current measurement
Comp. Over Cur. Warn F23
Compressor electricity is large
The compressor over-current protection
Input Over Cur. Warn F24
Input current is too large
Check and adjust the current measurement
EEPROM Error Warn
F25
MCU error
Check whether the chip is damaged
Replace the chip
V15V over/
undervoltage fault
F28
The V15V is overload or undervoltage
Check the V15V input voltage in range
13.5v~16.5v or not
Meaning
Default
Remarks
Refrigeration target temperature set point
27°C
Adjustable
Heating the target temperature set point
27°C
Adjustable
Automatic target temperature set point
27°C
Adjustable
(2) Parameter list